h1
A
Branch Pipe
Main Pipe
Distributor
Distributor
B
h2
Distributor Type
Installation of Indoor, Outdoor Unit
Installation Manual
7
ENGLISH
Distributor Type
(m)
Piping length and elevation
36k
100
40
60
20
30
15
42k
125
55
70
20
30
15
48k
135
55
80
20
30
15
54k
145
55
90
20
30
15
Capacity
(Btu/h)
Total Length
Max Main Pipe
Length (A/B)
Total Branch
Pipe Length
Max Branch
Pipe Length
Max Elevation
(h1)
In - In Elevation
(h2)
CAUTION: Capacity is based on standard length and maximum allowance
length is on the basis of reliability. Oil trap should be installed every 5~7
meters.