Installation Manual
9
ENGLISH
Installation of Indoor, Outdoor Unit
Caution
Regulation for refrigerant leakage(in Europe)
: the amount of refrigerant leakage should satisfy the following equation for human
safety.
❐
If the above equation can not be satisfied, then follow the following steps.
- Selection of air conditioning system: select one of the next
1. Effective opening part Installation
2. Reconfirmation of outdoor unit capacity and piping length
3. Reduction of the amount of refrigerant
4. 2 or more security device installation of alarm for gas leakage
- Change indoor unit type
: installation position should be over 2m from the floor (Wall mounted type
→
Cassette type)
- Adoption of ventilation system
: choose ordinary ventilation system or building ventilation system
- Limitation in piping work
: design for earthquake-proof and prevention against thermal stress
Total amount of refrigerant in the system
0.3 ( kg / m
3
)
Volume of the room at which indoor unit of the least capacity is installed