Maximum Length of Pipe and Extra Charge of Refrigerant Charge
Installation
It does not matter which unit is higher.
Standard Length
A,B,C,D
A
B
C
D
A2UW146FA0/1/2
A2UW166FA0/1
A2UW186FA0
A3UW186FA0/1
7.5m
25m
25m
-
-
40m(A+B)
7.5m
20m
20m
-
-
30m(A+B)
A3UW246FA0
A4UW246FA0
7.5m
25m
25m
25m
-
50m(A+B+C)
A4UW24GFA0
A4UW30GFA0
A4UW306FA0
7.5m
25m
25m
25m
25m
70m(A+B+C+D)
Max piping length each indoor unit
Model
[Outdoor Unit]
Max total piping length
1.1 The maximun allowable level and piping length
15m
7.5m
A
B
C
D
[Outdoor Unit]
[Indoor Unit]
1. TPS Inverter Multi -Multi Piping Type
Indoor Unit Capacity
Pipe Size
Rated
Max
Additional
(Btu/h)
Gas
Liquid
Length Length
Refrigerant
7k, 9k, 12k
3/8"(9.52mm)
1/4"(6.35mm)
7.5m
25m
25g/m
18k, 24k
1/2"(12.7mm)
1/4"(6.35mm)
7.5m
25m
35g/m
1.2 Refrigerant Charge
❈
Extra refrigerant = (Extended length - Rated length) x Additional refrigerant