ARIA SOHO Hardware Description and Installation Manual
Issue 1
KSU INSTALLATION
Aug, 2006
14
3.2.5 Frame Ground Connection
It is very important that the frame of the ARIA SOHO System is grounded:
1. Turn the grounding screw counter clockwise to loosen, as shown in Figure 3.2.5.
2. Insert the grounding wire and tighten the screw.
3. Then connect the grounding wire to an appropriate ground source (refer to Caution).
FIGURE 3.2.5 GROUNDING THE KSU
CAUTION
The equipment should be connected to a socket-outlet with a protective ground connection.
For ground wire, green-and-yellow insulation is required and the cross-sectional area of the
conductor must be more than UL 1015 AWG#18 (1.0mm)). It is recommended that the ground
wire is shorter than 1m (3.28ft).
Proper grounding is very important to protect the ARIA SOHO from external noise or to reduce
the risk of electrocution in the event of lightning strike.
Be sure to comply with applicable local regulations.
3.2.6 External Backup Battery Installation
In case of power failure, the external backup batteries automatically maintain uninterrupted power for the ARIA SOHO
System. The external batteries must provide 24V DC; this is generally accomplished by connecting two 12V batteries
in a series arrangement as shown: