PowerGATE

®

 ReadySwitch

Installation

The installation of the PowerGATE® ReadySwitch™ should 

be carried out by qualified personnel in accordance with local 

electrical codes.

Step 1: Fasten the PowerGATE® ReadySwitch™ to secure 

location

NOTE: The PowerGATE® ReadySwitch™ weighs 252 lbs. 

without attached cables.

1.  The panel should be located so there is adequate room for 

the externally connected cables to hang below the panel
A.  Typically allow a minimum of 36” clearance from 

the bottom of the panel to finished ground level

2.  Installation must be level and plumb to allow for proper 

drainage from PowerGATE® ReadySwitch™ weep holes

3.  Fastening onto an external wall using 3/8” fasteners must 

be completed prior to proceeding with any terminations (See 

Figure 1 for hole spacing)

Step 2: Installing the Conduit

NOTE: Conduit to enter through top or right/left side (No bottom 

feed -See Figure 5B)

NOTE: To maintain outdoor rating compliance for the enclosure, 

proper sealing procedures must be followed. This is to include, 

but not limited to, the use of proper gaskets.

NOTE: In order to prevent enclosure damage and to attain the 

enclosure requirements, the conduit must be aligned to prevent 

unnecessary stress on the enclosure walls.

1.  Open up door to expose dead front panel
2.  Unfasten the dead front panel by removing the hardware 

securing it (See Figure 5 and 5A)

3.  Conduit to be sized according to cabling rating

A.  400 Amp cable range #6-500MCM

4.  It is recommended that a knockout punch be used to cut hole 

for conduit
A.  Place the punch on the inside of the enclosure and draw 

the punch through to the die on the outside

5.  Vacuum entire upper chamber to ensure no shavings are left 

behind

Figure 5A

Figure 5

Front view with hinged cover 

removed

Front view with dead front 

panel removed

Front view with dead-front 

panel removed

Front view with hinged cover removed

Figure 5B

Содержание PowerGATE ReadySwitch

Страница 1: ...fety andreliability U S PatentMechanicalInterlockfor safeconnection Utility Generatordisconnects Hingeddoorwithkeylockentry SuitableforuseasService Equipment USOnly LM RS400 Rev 003 ReadySwitch 400 Am...

Страница 2: ...ls for Replacement Parts List 11 Appendix E Warning Location 12 Appendix F Specifications Contact Lex Products 800 643 4460 info lexproducts com 2 Important This manual contains information critical t...

Страница 3: ...tdoors only The mounting location is to be carefully selected to allow convenient connection to a generator and located a suitable distance away from any building openings or HVAC inlets Proper cleara...

Страница 4: ...s only 11 1 4 inches deep Individual cable entry holes restrict access reducing cable theft Enclosure is cULus Listed Type 3R Rainproof Keyed entry prevents unauthorized access and operation Cables dr...

Страница 5: ...E Conduit to enter through top or right left side No bottom feed See Figure 5B NOTE To maintain outdoor rating compliance for the enclosure proper sealing procedures must be followed This is to includ...

Страница 6: ...Contact Lex Products 800 643 4460 info lexproducts com 6 PowerGATE ReadySwitch Figure 6 Figure 6A Figure 6B...

Страница 7: ...A MAIN TERMINAL B BUILDING TERMINAL 8 Replace dead front panel and secure using hardware Place rotation label here Model Rating S N Transfer Switch Accessory Made in USA www lexproducts com 1 800 643...

Страница 8: ...vermin door is un obstructed and that the cable can flow freely through cable entry holes 3 Complete the Ground green connections first by feeding the cable through the appropriate port beginning with...

Страница 9: ...right Proper disconnection See Figure 9 A Grasp connector jacket firmly and rotate cam connector clockwise until it stops B Firmly pull on connector until it separates from the plug C Set aside 4 Cont...

Страница 10: ...d and that cable can flow freely through cable entry holes Ensure that gaskets are pliable and no cracking exists Ensure that door hinges are secure and lubricated Ensure that hasps are intact and ope...

Страница 11: ...000 LBL PGIP W1 10519 2 025 LBL PGIP D2 N Manual Transfer Switch This Device Will Not Automatically Transfer ToAn Alternative Source Commutateur Manuel Ce dispositif ne transfert pas automatiquement u...

Страница 12: ...wder Coated Steel ANSI 61 Grey Dimensions 48 x30 x13 5 48 x30 x13 5 Approximate Weight 252 lbs 252 lbs Part Number PIPM0400 C C AJ GBXEE PIPM0400 S S AJ GBXFF Rating 400 Amp 3 Phase H H H N G 4 Pole 5...

Отзывы: