PowerGATE

®

 ReadySwitch

Installation

 – Initial Setup - Main Power (continued)

Step 3: Complete a Safety Test

Do not attempt to use the PowerGATE® ReadySwitch™ prior 

to installation and completing the Pre-Operation and Operation 

Checklist under Appendix A.

Step 4: Completing Set Up

1. Close utility and re-energize system
2. After ensuring system power, close the door of the 

PowerGATE® ReadySwitch™
3. Lock the door, marking the keys as appropriate

Connecting A Portable Generator

Step 1: Review Pre-Operation Checklist under Appendix A 

prior to operation (page 10)

WARNING 

 

– DO NOT ATTEMPT CONNECTION WHILE CIRCUITS ARE 

LIVE

 

– Do not use cables if they appear frayed 

 

– Do not use cable if connectors or plug do not seat properly

 

– Do not use cables if any copper cabling is exposed

 

– To limit risk of shock, disable generator automatic start to 

prevent unintended starting

Step 2: Determining phase rotation of generator

1. Disconnect generator from all loads if needed
2.  Connect a phase rotation meter to the output phases of the 

generator

3. Record generator phase rotation (clockwise or counter-

clockwise)

Figure 9

Connecting A Portable Generator

 (continued

Step 3: Making Cam Connections

1.  Open the front door of the PowerGATE® ReadySwitch™
2.  Ensure that the vermin door is un-obstructed and that the 

cable can flow freely through cable entry holes

3. 

Complete the Ground (green) connections first by feeding 

the cable through the appropriate port, beginning with the 

closest from the door to the left.

Proper connection (See Figure 9):

A. 

Grasp connector jacket and firmly insert Cam connector 

into Cam plug

B.  Push on connector jacket until connector fully seats in 

plug

C.  Rotate connector jacket counterclockwise until it stops.  

  (see Figure 9)

4.  Complete ALL Neutral connections prior to proceeding
5.  Complete the hot connections by feeding the cable through 

the appropriate port and connect to the CAM-Type connector 
A.  (BLACK/BROWN- PHASE A- LINE 1, RED/ORANGE- 

PHASE B- LINE 2, BLUE/YELLOW- PHASE C- LINE 3

B.  Utilize the notes concerning phase rotation below
C.  Should the phase rotation of the generator (as determined 

in Step 2.3. above) and utility power (label found on 

the inside of the door for the Cam connection chamber) 

match, connect the Hots as follows:

Generator Hot

PowerGATE® ReadySwitch™ Hot

A

A

B

B

C

C

D.  Should the phase rotation of the generator (as determined 

in Step 2.3. above) and utility power (label found on the 

inside of the door for the Cam connection chamber) NOT 

match, connect the Hots as follows:

Generator Hot

PowerGATE® ReadySwitch™ Hot

A

B

B

A

C

C

6.  Complete ALL Phase connections prior to proceeding

7.  Make sure all connections are right and secure

Step 3: Close and secure chamber door, allowing cables to 

exit through cable ports at bottom

Содержание PowerGATE ReadySwitch

Страница 1: ...fety andreliability U S PatentMechanicalInterlockfor safeconnection Utility Generatordisconnects Hingeddoorwithkeylockentry SuitableforuseasService Equipment USOnly LM RS400 Rev 003 ReadySwitch 400 Am...

Страница 2: ...ls for Replacement Parts List 11 Appendix E Warning Location 12 Appendix F Specifications Contact Lex Products 800 643 4460 info lexproducts com 2 Important This manual contains information critical t...

Страница 3: ...tdoors only The mounting location is to be carefully selected to allow convenient connection to a generator and located a suitable distance away from any building openings or HVAC inlets Proper cleara...

Страница 4: ...s only 11 1 4 inches deep Individual cable entry holes restrict access reducing cable theft Enclosure is cULus Listed Type 3R Rainproof Keyed entry prevents unauthorized access and operation Cables dr...

Страница 5: ...E Conduit to enter through top or right left side No bottom feed See Figure 5B NOTE To maintain outdoor rating compliance for the enclosure proper sealing procedures must be followed This is to includ...

Страница 6: ...Contact Lex Products 800 643 4460 info lexproducts com 6 PowerGATE ReadySwitch Figure 6 Figure 6A Figure 6B...

Страница 7: ...A MAIN TERMINAL B BUILDING TERMINAL 8 Replace dead front panel and secure using hardware Place rotation label here Model Rating S N Transfer Switch Accessory Made in USA www lexproducts com 1 800 643...

Страница 8: ...vermin door is un obstructed and that the cable can flow freely through cable entry holes 3 Complete the Ground green connections first by feeding the cable through the appropriate port beginning with...

Страница 9: ...right Proper disconnection See Figure 9 A Grasp connector jacket firmly and rotate cam connector clockwise until it stops B Firmly pull on connector until it separates from the plug C Set aside 4 Cont...

Страница 10: ...d and that cable can flow freely through cable entry holes Ensure that gaskets are pliable and no cracking exists Ensure that door hinges are secure and lubricated Ensure that hasps are intact and ope...

Страница 11: ...000 LBL PGIP W1 10519 2 025 LBL PGIP D2 N Manual Transfer Switch This Device Will Not Automatically Transfer ToAn Alternative Source Commutateur Manuel Ce dispositif ne transfert pas automatiquement u...

Страница 12: ...wder Coated Steel ANSI 61 Grey Dimensions 48 x30 x13 5 48 x30 x13 5 Approximate Weight 252 lbs 252 lbs Part Number PIPM0400 C C AJ GBXEE PIPM0400 S S AJ GBXFF Rating 400 Amp 3 Phase H H H N G 4 Pole 5...

Отзывы: