4.3.7 Installation of RS485 Fieldbus for Flow Control Arrays
shows a flow control arrangement with the
RS485
fieldbus and its basic specifications.
Figure 25: Flow control array arrangement with RS485 fieldbus
Following points and information shall be considered:
➔
Testing has been done with arrangements of 8 systems. Higher number is possible but it is recommended to contact
Levitronix
®
Technical Service
department (see
Section 8
) for details and support.
➔
Address setting of the pump units can be done with the
Levitronix
®
Service Software
and a
PC. A USB/RS485
converter cable with integrated initialization network can be ordered according to
➔
The
RS485
protocol for master communication is available at
Levitronix
®
on request.
➔
Do not use multiple master systems at the same time.
➔
Do not use closed ring arrangements.
4.4 Electrical Installation of Flow Sensor
1. Every sensor comes delivered with a calibration sheet. Check if the S/N on the calibration sheet corresponds to the
S/N on the type label of the sensor.
2. Please store the delivered calibration sheet or its data on a defined storage place in order to be able to refer to it in
case of problems.
3. Attach one of the sensor extension cables (
Position 10a
) coming from the driver to the sensor connector.
4. When applying power, the flow control drivers needs about 10 seconds for a start-up procedure to be ready. In order
to get stable temperature and signals for flow converter and sensor 30 minutes shall be waited after power-on.
5. After start-up a Zero adjustment is recommended as described in
Section 4.8
Integrated Flow
Control Driver
OEM Model
#1
Integrated Flow
Control Driver
OEM Model
#2
Integrated Flow
Control Driver
OEM Model
#N
24 VDC
Supply
IPS Cable Hybrid
Single-Use
Pump Head
Single-Use
Pump Head
Single-Use
Pump Head
Flow
Sensor
Flow
Sensor
Flow
Sensor
120
120
510
510
Master
5V
Main Bus Line: < 100 m
Shielded cable with twisted wires recommended.
Termination:
Recommended for main bus line Length > 5m.
Initialization Network:
Always recommended.
To be implemented at the master.
Branch Bus Lines:
Length sum of all < 33 m
24 VDC
Supply
24 VDC
Supply
RS485+
RS485-