The transformer is connected to the 24VAC terminals.  The battery is connected using the battery cable 
connected to the board.   

Each Expansion Enclosure MUST be grounded in ONE of two possible ways: 

1. Earth ground each Expansion Enclosure to the same earth ground as the controller.

- OR -

2. Connect the Earth Ground terminal of each Expansion Enclosure to the Earth Ground terminal of the

controller using a separate conductor.  In this case, do not connect the Expansion Enclosure to a
separate earth ground.

The controller and Expansion Enclosure(s) grounds must be connected together or to the same earth 
ground to prevent any current from flowing through the RS-485 data bus (connections A and B).  If 
grounding is not as specified here, there is the possibility that the controller and Expansion Enclosure 
may lose communications, resulting in all zones in the Expansion Enclosure going into trouble or alarm, 
as required by UL. 

24 HOUR BATTERY BACKUP OPTION 

For extended battery backup time, a second 12V 7Ah battery can be installed - 

See

 Figure 5 - “24 Hour 

Standby Connections”.  Maximum total current load is reduced to 0.4 amps. 

ADDRESS SETTINGS 

DIP switch "S1" is used to set the communications address for the Expansion Enclosure. Up to four 
Expansion Enclosures can be addressed and used with OmniPro and up to eight Expansion Enclosures 
can be addressed and used with OmniPro II.   

Expansion Enclosures 1-4 are addressed by setting the corresponding switch to on and all others off.  
For example, to set the address for the first Expansion Enclosure, set switch S1-1 on and all others off; 
for the second, set switch S1-2 on and all others off.  The third and fourth are addressed similarly, using 
S1-3 and S1-4, respectively. 

Expansion Enclosures 5-8 are addressed by using the sum of all switches set to on.  For example, to set 
the address for the fifth Expansion Enclosure, set switch S1-1 and S1-4 on and all others off.  To address 
the sixth Expansion Enclosure, set S1-2 and S1-4 on and all others off.  To address the seventh 
Expansion Enclosure, set S1-3 and S1-4 on and all others off.  To address the eighth Expansion 
Enclosure, set S1-1, S1-3, and S1-4 on and all others off. 

Multiple switch combinations are possible for certain addresses.  For example, to set the address for the 
fifth Expansion Enclosure, you can set S1-1 and S1-4 on and all others off 

or

 you can set S1-2 and S1-3 

and all others off. 

W

EB VER

S

ION

www.

.com

[email protected]

1.800.561.8187

Содержание 17A00

Страница 1: ...Model 17A00 Expansion Enclosure Installation Manual WEB VERSION www com information itm com 1 800 561 8187 ...

Страница 2: ...1HYHU SXVK REMHFWV RI DQ NLQG LQWR WKLV SURGXFW WKURXJK RSHQLQJV DV WKH PD WRXFK GDQJHURXV YROWDJHV 1HYHU LQVWDOO FRPPXQLFDWLRQV ZLULQJ RU FRPSRQHQWV GXULQJ D OLJKWQLQJ VWRUP XVH LQ ZHW ORFDWLRQV 1HYHU WRXFK XQLQVXODWHG ZLUHV RU WHUPLQDOV XQOHVV WKH ZLULQJ KDV EHHQ GLVFRQQHFWHG DW WKH QHWZRUN LQWHUIDFH 8VH FDXWLRQ ZKHQ LQVWDOOLQJ RU PRGLI LQJ FRPPXQLFDWLRQV ZLULQJ RU FRPSRQHQWV 6 9 7 6 16758 7 216...

Страница 3: ...2 POWER SUPPLY CHECKOUT 12 COMMUNICATIONS CHECKOUT 13 BURGLARY ZONE CHECKOUT 13 FIRE ZONE CHECKOUT 14 OUTPUT CHECKOUT 14 TROUBLE CONDITIONS 14 UNDERWRITER S LABORATORIES UL REQUIREMENTS 15 FEDERAL COMMUNICATIONS COMMISSION FCC NOTICE 16 SMOKE DETECTOR INSTALLATION GUIDELINES 16 FIGURE 1 MODEL 17A00 HOOKUP 3 FIGURE 2 OVERALL CONNECTIONS DIAGRAM 5 FIGURE 3 FIRE ZONE CONNECTIONS 7 FIGURE 4 RELAY MODU...

Страница 4: ...le two conductor cable Each of the zone inputs may be used as a burglary zone a fire zone a temperature zone or an auxiliary input Each zone may also be used for connection of a Model 1101 Programmable Energy Saver Module PESM The Expansion Enclosure provides 16 general purpose voltage outputs These voltage outputs can be used to operate 12VDC relays or other low voltage switching applications The...

Страница 5: ...mps ADDRESS SETTINGS DIP switch S1 is used to set the communications address for the Expansion Enclosure Up to four Expansion Enclosures can be addressed and used with OmniPro and up to eight Expansion Enclosures can be addressed and used with OmniPro II Expansion Enclosures 1 4 are addressed by setting the corresponding switch to on and all others off For example to set the address for the first ...

Страница 6: ...Page 3 FIGURE 1 MODEL 17A00 HOOKUP WEB VERSION www com information itm com 1 800 561 8187 ...

Страница 7: ...rs and other security devices meet this requirement An external 1000 ohm end of line resistor must be used for all burglary zones Connect the loop to the and terminals for the desired zone 1 When using a normally open switch a 1000 ohm end of line resistor must be in parallel with the zone being used Maximum loop resistance excluding end of line resistor should not exceed 150 ohms 2 When using a n...

Страница 8: ...Page 5 NOTE FIGURE 2 OVERALL CONNECTIONS DIAGRAM WEB VERSION www com information itm com 1 800 561 8187 ...

Страница 9: ...losed for alarm 4 wire SYSTEM type smoke detectors ESL Model 445AT or equivalent rated 8 14 VDC 2 Power smoke detectors from SWITCH 12 VDC 3 End of line resistor 1000 ohms The maximum loop resistance EXCLUDING the end of line resistor is 150 ohms 4 Use LEVITON Model 1503A0011 End Of Line Resistor Assembly in UL Listed Installations 5 End of Line Relay Module ESL Model 204B or equiv required for UL...

Страница 10: ...Page 7 FIGURE 3 FIRE ZONE CONNECTIONS WEB VERSION www com information itm com 1 800 561 8187 ...

Страница 11: ...cuit breakers silent relays for high voltage current applications sprinkler valves pool pump controls and various other low voltage switching applications Connect the green pigtail wire J1 to ground GND on the Expansion Enclosure Each relay on the Relay Module will use one voltage outputs on the Expansion Enclosure Each output is connected to one of the trigger inputs T1 T8 When an output unit is ...

Страница 12: ...Page 9 FIGURE 4 RELAY MODULE CONNECTIONS WEB VERSION www com information itm com 1 800 561 8187 ...

Страница 13: ...VDC GND Terminal 2 Red Wire to AUXILIARY 12VDC terminal Terminal 3 Yellow Wire to the ZONE terminal An outdoor temperature sensor mounts in an outdoor location usually under an overhang and sends the outdoor temperature the Expansion Enclosure It is coated with a sealant to withstand outdoor moisture The outdoor temperature can be displayed on the console spoken over the telephone or displayed on ...

Страница 14: ...Page 11 24 HOUR STANDBY Maximum current ratings for 24 hours Auxiliary 12V Switch 12 V and Outputs 1 16 400 Ma WEB VERSION www com information itm com 1 800 561 8187 ...

Страница 15: ...puts Bypass all panic tamper and fire zones POWER SUPPLY CHECKOUT 1 Disconnect the positive red wire to the battery Make sure that it is not touching anything 2 Plug in the power transformer The AC ON LED should illuminate The STATUS LED should begin blinking which indicates that the processor and software are working properly 3 Unplug the power transformer to turn off the system Connect the red b...

Страница 16: ...all doors and windows are closed all motion detectors and security devices are normal and all fire sensors are reset 1 Restore all security zones Verify that the console reads SYSTEM OK 2 Check the wiring for any zones that are in alarm or in trouble 3 Have a partner go around the house and trip each sensor one at a time The display should indicate the correct zone when the zone is tripped then re...

Страница 17: ...CHECKOUT Command each voltage output individually Verify that the correct device is activated Verify that the device is turned on when an ON command is issued and turned off when an OFF command is issued For a complete list of output unit numbers refer to the controller Owner s Manual that was supplied with the system TROUBLE CONDITIONS The Expansion Enclosure reports the following trouble conditi...

Страница 18: ...l be the Revere P N RT 2440SL and 2 12 V 7 amp hour batteries 2 If used in UL applications the Model 17A00 and the controller shall be configured for 24 hour Standby Time as shown under 24 HOUR STANDBY CONNECTIONS diagram in this manual Maximum current ratings for 24 hours must be observed 3 Burglary Zone Hookup using LEVITON P N 393 1K 1000 ohm EOL resistor 4 Fire Zone Hookup using LEVITON P N 15...

Страница 19: ... Do not install smoke detectors where normal ambient temperatures are above 100 F 37 8 C or below 40 F 4 C Also do not locate the detector in front of air conditioners heating registers or other locations where normal air circulation will keep smoke form entering the detector 3 Additional information on Household Fire Warning is available at nominal cost from The National Fire Protection Associati...

Страница 20: ...LJQHG WR SURYLGH UHDVRQDEOH SURWHFWLRQ DJDLQVW KDUPIXO LQWHUIHUHQFH LQ D UHVLGHQWLDO LQVWDOODWLRQ 7KLV HTXLSPHQW JHQHUDWHV XVHV DQG FDQ UDGLDWH UDGLR IUHTXHQF HQHUJ DQG LI QRW LQVWDOOHG DQG XVHG LQ DFFRUGDQFH ZLWK WKH LQVWUXFWLRQV PD FDXVH KDUPIXO LQWHUIHUHQFH WR UDGLR FRPPXQLFDWLRQV RZHYHU WKHUH LV QR JXDUDQWHH WKDW LQWHUIHUHQFH ZLOO QRW RFFXU LQ D SDUWLFXODU LQVWDOODWLRQ I WKLV HTXLSPHQW GRHV FD...

Страница 21: ...LER OR AN EXPERIENCED RADIO 46 TECHNICIAN FOR HELP LEVITON LIMITED WARRANTY Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that products manufactured by Leviton under the Leviton brand name Product will be free from defects in material and workmanship for the time periods indicated below whichever is shorter s MNI0R O AND UMINA 0R O three 3 years from ins...

Отзывы: