COMMUNICATIONS HOOKUP
The Expansion Enclosure communicates with the controller using the same wires that connect the
consoles to the controller. The communications wires for the Expansion Enclosure and consoles may be
homerun to the controller or daisy-chained to each other.
Connect the terminals marked "A" and "B" on the Expansion Enclosure to the corresponding terminals
on the controller or console. The Expansion Enclosure may be located up to 1000 feet away from the
controller.
SECURITY ZONE HOOKUPS
Each of the 16 security zone inputs may be used as a burglary zone, a fire zone, a temperature zone, an
auxiliary input, or for connection of Model 1101 Programmable Energy Saver Modules.
The system supports a maximum loop resistance, excluding the end-of-line resistor, of 150 ohms.
The default settings for all zone inputs are configured as Auxiliary inputs.
BURGLARY ZONE HOOKUP
The system supports both normally open and normally closed switches. Most contacts designed for
doors, windows, motion detectors, glassbreak detectors and other security devices meet this requirement.
An external 1000 ohm end-of-line resistor must be used for all burglary zones. Connect the loop to the
"+" and "-" terminals for the desired zone.
1. When using a normally open switch, a 1000 ohm end-of-line resistor must be in parallel with the
zone being used. Maximum loop resistance excluding end-of-line resistor should not exceed
150 ohms.
2. When using a normally closed switch, a 1000 ohm end-of-line resistor must be put in series with
the zone being used. Maximum loop resistance excluding end-of-line resistor should not exceed
150 ohms.
3. Power motion detectors from AUXILIARY 12VDC.
4. Those sensors that latch alarms and can only be cleared by cycling power, such as some
glassbreak detectors, should be powered from SWITCH 12VDC.
5. Unused zones may be left open, and should be left at the default setting of AUXILIARY zone
types.
6. Use normally open or normally closed panic switches with a 1000 ohm end-of-line resistor.
It is also possible to use a switch or open collector output that shorts to ground or +12VDC.
Connect the switch to the "+" terminal for the zone. Connect the external end-of-line resistor
between the "+" and "-" terminals.
W
EB VER
S
ION
www.
.com
1.800.561.8187
Содержание 17A00
Страница 6: ...Page 3 FIGURE 1 MODEL 17A00 HOOKUP WEB VERSION www com information itm com 1 800 561 8187 ...
Страница 10: ...Page 7 FIGURE 3 FIRE ZONE CONNECTIONS WEB VERSION www com information itm com 1 800 561 8187 ...
Страница 12: ...Page 9 FIGURE 4 RELAY MODULE CONNECTIONS WEB VERSION www com information itm com 1 800 561 8187 ...