COMMUNICATIONS CHECKOUT
The STATUS LED blinks at a rate of one blink per second if the Expansion Enclosure is communicating
properly with the controller. If the STATUS LED blinks at a rate of four blinks per second, it indicates
that the Expansion Enclosure is not communicating properly. In this case, check the following:
1. Verify that the "A" and "B" terminals on the Expansion Enclosure are connected to the
corresponding "A" and "B" terminals on the controller. If the wiring for the Expansion
Enclosure is daisy-chained to a console, verify that the entire chain is connected properly.
2. Verify that DIP switch S1 on the Expansion Enclosure is set properly.
3. Verify that the number of Expansion Enclosures has been properly set-up at the controller.
4. Verify that the controller is operating properly.
BURGLARY ZONE CHECKOUT
Check that all doors and windows are closed, all motion detectors and security devices are normal, and
all fire sensors are reset.
1. Restore all security zones. Verify that the console reads "SYSTEM OK".
2. Check the wiring for any zones that are in alarm or in trouble.
3. Have a partner go around the house and trip each sensor one at a time. The display should
indicate the correct zone when the zone is tripped, then return to "SYSTEM OK" when the zone
is secured. Be sure that the zone type indicated is correct for the zone being tested.
4. For sensors that latch alarms that can only be cleared by cycling the power to the sensor, it is
necessary to arm then disarm the system to clear the alarm condition.
5. If the zone being checked is armed (i.e. panic and tamper zones, which are always armed) the
alarm will be activated. Disarm the system following the alarm activation.
6. For a complete list of zone types and descriptions, refer to the controller Installation Manual that
was supplied with the system.
W
EB VER
S
ION
www.
.com
1.800.561.8187
Содержание 17A00
Страница 6: ...Page 3 FIGURE 1 MODEL 17A00 HOOKUP WEB VERSION www com information itm com 1 800 561 8187 ...
Страница 10: ...Page 7 FIGURE 3 FIRE ZONE CONNECTIONS WEB VERSION www com information itm com 1 800 561 8187 ...
Страница 12: ...Page 9 FIGURE 4 RELAY MODULE CONNECTIONS WEB VERSION www com information itm com 1 800 561 8187 ...