Test operation
The function capability of the test monitoring unit and the single beam safety light barrier
are tested during test operation.
To induce the test operation, the start input is activated (green LED).
As long as the start button is pressed, the TMC 66 remains in test operation.
After release of the start button, the TMC 66 changes from test operation to protection
mode.
The test operation is displayed through state "11" on the 7-segment display.
Protection mode
In protection mode, the function of the single beam safety light barrier is cyclically tested
every two seconds. The free protective field is displayed by the green LED.
Activation is used (green LED).
The safety outputs are closed which is displayed by a green LED.
Protection mode is displayed by state "21" on the 7-segment display.