Transmitting of the laser position value
#Leuze
#Leuze electronic
GmbH + Co KG, Postfach 11 11, D-73277 Owen/Teck, In der Braike1, D-73277 Owen/Teck, Tel. ++49 (0)7021/5730, Fax ++49 (0)7021/573199
Page 36 of 42
LZ - ELE - BA - GB - 0009 - 00
Date: 01.07.2003
6.1 Read/Write Service Data Object
The transfer of the Service Data Object (SDO) is done by the CMS Multiplexed
Domain protocol (CIA DS202/2).
6.1.1 Read SDO:
(Initiate Domain Upload)
Request Protocol format:
COB-Identifier = 600h + Node-ID
Read SDOs
Byte
0 1 2 3 4 5 6 7
content
Code
Index
Sub-
index
Data 0 Data 1 Data 2 Data 3
40h
low
high
byte
0
0
0
0
The Read SDO telegram has to be send to the slave.
The slave answers with the following telegram:
Response Protocol format:
COB-Identifier = 580h + Node-ID
Read SDOs
Byte
0 1 2 3 4 5 6 7
content
Code Index
Sub-
index
Data 0 Data 1 Data 2 Data 3
4xh
low
high
byte
data
data
data
data
Format byte 0:
MSB
LSB
7 6
5
4
3
2
1
0
0 1 0 0
n
1 1
n = number of data bytes ( bytes 4-7) that does not contain data.
If only 1 data byte (Data 0) contains data the value of byte 0 is "4FH".
If byte 0 = 80h the transfer has been aborted.