Commissioning / Installation
#Leuze electronic
GmbH + Co KG, Postfach 11 11, D-73277 Owen/Teck, In der Braike1, D-73277 Owen/Teck, Tel. ++49 (0)7021/5730, Fax ++49 (0)7021/573199
Date: 01.07.2003
LZ - ELE - BA - GB - 0009 - 00
Page 19 of 42
3.2.3 The communication profile
Two process data objects (PDO) are implemented in the device. One is used for
asynchronous transmission and the other one for the cyclic transmission functions.
The output position value is transmitted in binary code:
COB-ID
Output Position Value
11 Bit
Byte 0
Byte 1
Byte 2
Byte 3
2
7
to 2
0
2
15
to 2
8
2
23
to 2
16
2
31
to 2
24
3.2.3.1 1
st
Transmit Process Data Object (asynchronous)
This PDO transmit the position value of the laser in an asynchronous way. The cyclic
timer is stored in index 6200h.
Index Sub-Index Comment
Default Value
1800h
0
number of supported entries
3
1
COB-ID used by PDO 1
180h + Node-ID
2
transmission type
254
3
inhibit time
0
1A00h 0
number of mapped objects
1
1
Position value
60040020h
3.2.3.2 2
nd
Transmit Process Data Object (synchronous)
This PDO transmit the position value of the laser in a cyclic way (on request). Request
by remote frame and/or sync telegrams.
Index Sub-Index Comment
Default Value
1802h
0
number of supported entries
3
1
COB-ID used by PDO 2
280 + Node-ID
2
transmission type
1
3
inhibit time
0
1A02h 0
number of mapped objects
1
1
Position value
60040020h