Configuration / Parameter Setting
#Leuze electronic
GmbH + Co KG, Postfach 11 11, D-73277 Owen/Teck, In der Braike1, D-73277 Owen/Teck, Tel. ++49 (0)7021/5730, Fax ++49 (0)7021/573199
Date: 01.07.2003
LZ - ELE - BA - GB - 0009 - 00
Page 29 of 42
4.1.1.4 Object 2004 - Automatic error acknowledgement
Determines, whether occurring error reports should be cleared automatically after
eliminating the trouble.
Unsigned8, Read/Write
0
not automatically
(default)
An occurring error report can be cleared via "Object 1003h:
", S22 or via "Object 2003 - Function external input", S28.
1 automatically
An occurring error report is cleared automatically after
remedying of the error.
4.1.1.5 Object 2005 – Function error output
Determines, the function of the error output (external switching output). Definition of
the error see "Description of the error code", S22.
Unsigned8, Read/Write
0 disabled
(default)
1 Temperature
2 Intensity
3 Hardware
4 all
errors
4.1.1.6 Object 2006 – Switching functions
Unsigned8, Read/Write
Switch off laser diode
Bit 0 = 1
By setting this bit the laser diode (LD) is switched off for
the extension of the life time. If in "Object 2003 - Function
external input", S28 = "LD-switching input" is preselected,
or in the PC-program "OMSConfiguration-Tool" in the
basic parameters the switching-off of the laser diode is
carried out automatically, this function is ineffective.
Switch on laser diode
Bit 1 = 1
By setting this bit the laser diode is switched on. This
function is ineffective if: see "Switch off laser diode" above.
Execute Preset
Bit 2 = 1
By setting this bit the laser is adjusted to the value
deposited in "Object 6003h – Preset Value", S30.
A read access returns the status of the laser diode:
0
Laser diode is switched off
1
Laser diode is switched on