It is absolutely necessary to connect functional earth, since all electrical interference (EM
pick-up) is discharged via the functional earth connection.
5.3.4
Termination of the RS 485 interface
A permanently installed termination network is present in the MA 8-01. The network termi-
nates the outgoing RS 485 data interface, as shown in figure 5.2, and cannot be switched
off.
Figure 5.2:
Termination of the RS 485 interface in the MA 8-01
5 V
GND
390
Ω
390
Ω
220
Ω
RS 485 A
RS 485 B
RS 485 receive/transmit data
A-line (P), pin 2
RS 485 receive/transmit data
B-line (N), pin 4