KMD1060E
14
5.2 LED OFF Time Setting
The next parameter that can be changed is the amount of time that the LED is OFF during a
cycle. The time can be increased or decreased using the
UP
or
DOWN
buttons. The LED
OFF time can be set with the following limits:
Time Base
Min Time
Max Time
0.1 sec
.3 sec
5.9 sec
1.0 sec
6 secs
60 secs
The time base automatically changes at 6 seconds. Once this parameter is set press
OK
to
continue.
5.3 Cycle Count
The next parameter that can be changed is the number of cycles that will run during a single
iteration. The number of cycles can be increased or decreased using the
UP
or
DOWN
buttons. The maximum number of cycles that can be run during a single iteration is 255.
Once this parameter is set press
OK
to continue.
5.4 Save Parameter Changes
At this point all the parameters have been changed to the user’s preferences. These
changes have not been saved to memory, and if they are not, all parameters will revert back
to the previous values. At this point the user is prompted to save the changes. Determine if
you would like to save the changes to memory and make your selection using the
UP
or
DOWN
button. Once the selection has been made press
OK
to continue.
** NOTE **
At any time, while making changes to the parameters, the user pauses for longer
than 7sec, the display will return to the “SYSTEM READY” screen. No changes
will be saved.
5.5 Power Adjustments
The adjustment control has 10 turns. Make clockwise turns to increase power output (+) and
counter clockwise turns to decrease power output (-). The unit is set to full power (completely
clockwise position) from factory.
Note: Radiometer is required in order to determine UV output.