50
PARAMETER SETTING MANUAL
VARMECA 20
Variable speed motors and geared motors
COMMISSIONING THE CDC-VMA 20 CONSOLE
LEROY-SOMER
3532 - 05.2004 / f
2.3 - Read mode
- Connect the console to the VARMECA 20 RS 232 socket.
- Power up the VARMECA 20.
- On power-up, the console display is positioned on the 1st
parameter P01 F-MIN.
The 1st line of the display indicates the parameter
description.
The 2nd line indicates the parameter value and its unit of
measurement.
The
key scrolls through the parameters.
The
key is used for scrolling in the opposite direction.
2.4 - Parameter setting mode
• Parameter modifications must be made with the
VARMECA 20 stopped (run command disabled).
To modify a setting, use the
or
keys to access the
parameter.
The
key is used to make the parameter to be modified
flash.
Modify the setting value with the
or
keys.
As soon as the value differs from the value memorised, the
message M ? appears.
When the desired setting value has been reached, it can be
memorised using the
key.
M ? disappears from the display.
The
key is used to quit parameter-setting mode.
MEM.
2.5 - VARMECA 20 parameters
List and description of the parameters which can be accessed by the CDC-VMA 20 console
Display
Description
Adjustment range
Factory setting
VMA A20
VMA B20
P01 F-MIN
Minimum operating frequency
6 to Fmax
12Hz
P02 REF 0V/4mA
Calibration of the 0V or 4mA min. reference
0 to Fmax
12Hz
P03 F-MAX
Maximum operating frequency
32 to 220Hz
32 to 100Hz
50 or 80Hz
P04 REF 10V/20mA
Calibration of the 10V or 20mA max. reference
32 to 220Hz
32 to 100Hz
50 or 80Hz
P05 ACCEL RAMP
*
Acceleration ramp
Ramp value to switch from 0 to 50Hz
0 to 100s
0 to 40s
3s
Incrementation
In the standard configuration, terminals 9 and
10 must be connected together in order to
modify the value of the acceleration ramp.
1s
0.1s
P06 DECEL RAMP
*
Deceleration ramp
Ramp value to switch from 50 to 0Hz
0 to 100s
0 to 40s
3s
Incrementation
In the standard configuration, terminals 9 and
10 must be connected together in order to
modify the value of the deceleration ramp.
1s
0.1s
P07 STOP MODE
*
Stop mode
ramp, freewheel or
automatic
ramp or freewheel
ramp
Freewheel
= freewheel stop
ramp
= stop following ramp
automatic
= controlled deceleration
P08 UN-MOT
Voltage applied to the motor at frequency
0 to 480V
230 or 400V
base
P09 FN-MOT
Base frequency of motor
50 to Fmax
50Hz
P10 CONTROL U/F
*
Selection of voltage/frequency ratio
constant or dynamic
constant = fixed U/F
Voltage P08 will be applied at the point of
constant from
frequency P09
0.25 to 1.1Kw
dynamic = dynamic U/F
dynamic from
The voltage adapts automatically to the
1.5 to 4Kw
motor load (position of mini dip switch
K3 = OFF)
*
This parameter can be modified if the VARMECA is powered up and a stop command has been issued.