70
PARAMETER SETTING MANUAL
VARMECA 20
Variable speed motors and geared motors
WIRING DIAGRAMS
LEROY-SOMER
3532 - 05.2004 / f
4.3 - Configuration 1: 2 preset speeds and analogue reference - 2 running directions
Marking
Functions - Characteristics
Connection of protected mains supply phases
L1, L2 or 200V to 240V ± 10% 50-60Hz in single-phase
L1, L2, L3 220V to 480V ± 10%, 50-60Hz in three-phase
PE
Earth connection
R1, R2
Connection of the braking resistor (optional)
VMA21 - min. resistance value = 200 Ohms
VMA22 - min. resistance value = 200 Ohms
1
Locking logic input
Terminals 1 and 3 not connected: drive disabled
Terminals 1 and 3 connected: drive enabled
2
Reference selection logic input
3
24VDC, 30mA
Common at terminal 10
4
10V, 10mA
5
0 V
6
Reference input 0 to +10V or 4-20mA
0-10V: input impedance = 100kOhms
4-20mA: input impedance = 0.5kOhms
7
Reverse/Stop logic input
8
Forward/Stop logic input
9
Reference selection logic input
10
24VDC, 30mA
Common at terminal 3
11, 12
Fault relay - volt-free contact 250V 1A
Contact open: switched off or faulty
Contact closed: running
1
2
3
4
L1
L2
L3
R1
R2
PE
5
6
7
8
9
10
+24V
11
12
QS : Fused isolator
AU : Emergency stop
SB1 : Off button
SB2 : On button
Control
potentiometer
0V
+10V
+24V
Run reverse
Run forward
Selection of
preset speeds
Fault relay
VARMECA 20
QS
KM1
SB2
KM1
SB1
AU
Remote control
power supply
KM1
Braking
resistor
(Optional)
Analogue reference
selection
S2
S1
Mains
power supply
Associated parameter setting
For other parameter settings see sections 2 and 3.
CDC-VMA 20
PEGASE VMA 20
P14 = Config. 1
Terminal block configuration = Config. 1
P15 = VP1-1(Hz)
VP1 = option 1-4
P16 = VP2-1(Hz)
VP2 option 1-4 or VP1 option 2
P60 = ON for materials
Dynamic control = YES for
materials handling applications
handling applications
Reference
S1
S2
VP1-1
1
0
VP2-1
0
0
Analogue reference
-
1