Installation and maintenance
D510 c
Automatic Voltage Regulators (AVRs)
38
4243 en - 2012.10 / e
LEROY-SOMER
5. These 2 indications show that the AVR is connected and its characteristics have been selected.
6. 2-signal display screen. Simply tick in one of the boxes (R or B) and set the scale (Max-Min).
7. The CT phase angle should be compensated to improve the accuracy of the display by moving
the «CT phase angle correction» slider.
8. Transient test:
Do not start this test if in load operation.
- Click on «Transient test»,
- The test voltage level setting window appears,
- Enter the values, confirm, wait for the process to end.
Note:
Set the minimum and maximum values within the range permitted by the generator
voltage sensing device.
9. To start reading, click «Start reading». The filter value can be adjusted by 0.1 s to 3 s.
10. The voltage to track is displayed and can be adjusted thanks to the buttons
.
The setting of Underspeed is also directly accessible.
The approach is the same for the other regulation modes (PF, kVAR et Iexc)