ESPANOL
8
Instalación
Tipo
Instalación conforme a EN 60204-1
Instalación conforme a UL
DPT
(2)
.
Fusible
Fusible
automático
L1, L2, L3, PE
[mm
2
]
Fusible
(3)
L1, L2, L3, PE
[AWG]
1/N/PE
ETMD371L2YXA, ETMD551L2YXA
M10 A
C10 A
1,5
10 A
14
> 30 mA
ETMD751L2YXA
M16 A
C16 A
2,5
15 A
14
ETMD112L2YXA
M20 A
C20 A
2,5
15 A
12
ETMD152L2YXA
M25 A
C25 A
2,5
20 A
12
ETMD222L2YXA
M30 A
C30 A
4,0
30 A
10
3/PE
ETMD371L2YXA...ETMD112L2_XA
(4)
M10 A
C10 A
1,5
10 A
14
ETMD152L2_XA
(4)
M16 A
C16 A
1,5
12 A
14
ETMD222L2_XA
(4)
M16 A
C16 A
2,5
15 A
12
ETMD402L2TXA
M25 A
C25 A
4,0
25 A
10
ETMD552L2TXA
M40 A
C40 A
6,0
35 A
8
ETMD752L2TXA
M50 A
C50 A
10
45 A
8
ETMD371L4TXA...ETMD222L4TXA
M10 A
C10 A
1,5
10 A
14
ETMD302L4TXA
M16 A
C16 A
1,5
12 A
14
ETMD402L4TXA
M16 A
C16 A
2,5
15 A
14
ETMD552L4TXA
M20 A
C20 A
2,5
20 A
12
ETMD752L4TXA
M25 A
C25 A
4,0
25 A
10
(1) Cumpla las normas locales aplicables
(2) Disyuntor de fuga a tierra sensible a la corriente por impulsos o a la corriente universal
(3) Fusibles de limitación de corriente que actúan rápido de clase CC o T de UL, 200,000 AIC, necesarios.
Bussman KTK-R, JJN, JJS, o equivalente
(4) “_” = Y o T; los regímenes son los mismos para cualquier modelo con entrada 3/PE
EMC
Cumplimiento de la norma EN 61800-3/A11
Emisión de ruidos
Cumplimiento del valor límite de clase A conforme a la norma EN 55011 si se instala
en un armario de control con el filtro adecuado y la longitud del cable no supera los
10 m
A Abrazaderas de blindaje
B Cable de control
C Cable del motor de baja capacitancia
(núcleo/núcleo
<
75 pF/m, núcleo/blindaje
<
150 pF/m)
D Placa de montaje conductora
E Filtro
Tmd005
B
C
D
A
3.2
Instalación eléctrica
3.2.1 Instalación según los requisitos EMC
3.2.2 Secciones de fusibles/cables
E
(1)
Содержание Tmd
Страница 69: ...FRAN AIS 24 Notes...