10
ENGLISH
Installation
Terminal Data for control connections
(printed in
bold
= Lenze setting)
28
Digital input Start/Stop
LOW = Stop; HIGH = Run Enable
input resistance = 3.3 k
Ω
7
Reference common
8U
Analog input
0 … 10 V
(changeable under C34)
input resistance: >40 k
Ω
9
Internal DC supply for setpoint potenti10 V, max. 10 mA
A+
Internal DC supply for external devices
+12 V, max. 50 mA
A1
Digital output configurable with c17
DC 24 V / 50 mA
20
Internal DC supply for digital inputs
+15 V, max. 20 mA
20
E1
Digital input configurable with CE1
Activate fixed setpoint 1 (JOG1)
HIGH = JOG1 active
Both HIGH = JOG3 active
R
i
= 3.3 k
Ω
E2
Digital input configurable with CE2
Activate fixed setpoint 2 (JOG2)
HIGH = JOG2 active
E3
Digital input configurable with CE3
Activate DC injection brake (DCB)
HIGH = DCB active
E4
Digital input configurable with CE4
Direction of rotation
LOW = CW rotation
HIGH = CCW rotation
A2
Digital output configurable with c18
DC 24 V / 50 mA
8
I
Analog input (changeable under C34)
input resistance: 150
Ω
7
Reference common
62
Analog output configurable with c08...c11
0...10 V or 2...10 V, max. 20mA
71
RS-485 serial communication input
RXB/TXB (B+)
72
RS-485 serial communication input
RXA/TXA (A-)
LOW = 0 … +3 V, HIGH = +12 … +30 V
Protection against contact
• All terminals have a basic isolation (single insulating distance)
• Protection against contact can only be ensured by additional measures (i.e. double insulation)
3.2.4 Control terminals