19
ENGLISH
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Lenze Selection
7
Configuration TRIP
reset (error reset)
0
0
TRIP reset after LOW-HIGH change at
terminal 28, mains switching, or after
LOW-HIGH change at digital input
“TRIP reset”
1
Auto-TRIP reset
• Auto-TRIP reset after the time set in c71
• More than 8 errors in 10 minutes will
trigger
S
fault
WARNING!
Automatic starting/restarting may cause damage to equipment and/or injury to personnel!
Automatic starting/restarting should only be used on equipment that is inaccessible to
personnel.
7
Auto-TRIP reset delay
0.0
0.0
{s}
60.0 See c70
7
Input voltage selection
0
Low (for 200 or 400 V input)
• Lenze setting depends on C93
• During commissioning, confirm
correct setting based on mains voltage
1
High (for 230 or 480 V input)
7
Operating time counter
Display
Total time in status “Start”
0...999 h: format xxx
1000...9999 h: format x.xx (x1000)
10000...99999 h: format xx.x (x1000)
7
Mains connection time
counter
Display
Total time of mains = on
S-ramp integration
time
0.0
0.0
{s}
50.0 • c82 = 0.0: Linear accel/decel ramp
• c82 > 0.0: Adjusts S-ramp curve for
smoother ramp
Skip frequency 1
0.0
0.0
{Hz}
240
• L25 and L26 define the start of the skip
range
• L28 defines the bandwidth of the skip
range
Skip frequency 2
0.0
0.0
{Hz}
240
Skip frequency
bandwidth
0.0
0.0
{Hz}
10.0
Note
Bandwidth (Hz) = fs (Hz) + L28 (Hz) fs = L25 or L26
Example: L25 = 18 Hz and L28 = 4 Hz; the bandwidth = 18...22 Hz
LECOM power up
state
0
0
Quick stop
1
Inhibit
Serial time-out action
0
0
Not active
Selects controller reaction to serial timeout
1
Inhibit
2
Quick stop
3
Trip fault
Serial fault time
50
50
{ms}
65535
Sets the serial timeout length