8
ENGLISH
Installation
Type
Installation to EN 60204-1
Installation to UL
E.l.c.b.
(2)
Fuse
Miniature
circuit
breaker
L1, L2, L3, PE
[mm²]
Fuse
(3)
L1, L2, L3, PE
[AWG]
1/N/PE
ETMD371L2YXA, ETMD551L2YXA
M10 A
C10 A
1.5
10 A
14
> 30 mA
ETMD751L2YXA
M16 A
C16 A
2.5
15 A
14
ETMD112L2YXA
M20 A
C20 A
2.5
15 A
12
ETMD152L2YXA
M25 A
C25 A
2.5
20 A
12
ETMD222L2YXA
M30 A
C30 A
4.0
30 A
10
3/PE
ETMD371L2YXA...ETMD112L2_XA
(4)
M10 A
C10 A
1.5
10 A
14
ETMD152L2_XA
(4)
M16 A
C16 A
1.5
12 A
14
ETMD222L2_XA
(4)
M16 A
C16 A
2.5
15 A
12
ETMD402L2TXA
M25 A
C25 A
4.0
25 A
10
ETMD552L2TXA
M40 A
C40 A
6.0
35 A
8
ETMD752L2TXA
M50 A
C50 A
10
45 A
8
ETMD371L4TXA...ETMD222L4TXA
M10 A
C10 A
1.5
10 A
14
ETMD302L4TXA
M16 A
C16 A
1.5
12 A
14
ETMD402L4TXA
M16 A
C16 A
2.5
15 A
14
ETMD552L4TXA
M20 A
C20 A
2.5
20 A
12
ETMD752L4TXA
M25 A
C25 A
4.0
25 A
10
(1) Observe the applicable local regulations
(2) Pulse-current or universal-current sensitive earth leakage circuit breaker
(3) UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, required. Bussman KTK-R, JJN, JJS, or equivalent
(4) “_” = Y or T; the ratings are the same for either model with 3/PE input
EMC
Compliance with EN 61800-3/A11
Noise emission
Compliance with limit value class A according to EN 55011 if installed in a control
cabinet with the appropriate footprint filter and the motor cable length does not exceed
10m
A Screen clamps
B Control cable
C Low-capacitance motor cable
(core/core
<
75 pF/m, core/screen
<
150 pF/m)
D Electrically conductive mounting plate
E Filter
Tmd005
B
C
D
A
E
3.2.2 Fuses/cable cross-sections
3.2
Electrical installation
3.2.1 Installation according to EMC requirements
(1)
Содержание Tmd