Technical Data
2.2
SCL/SCM Model Designation Code
The SCL/SCM model number gives a full description of the basic drive unit.
EXAMPLE: SL210S = SCL Series, 208/240 Vac, 1 HP, single phase input
SL
2
10
S
Series:
SL = SCL Series Variable Speed AC Motor Drive with integral line filter
SM = SCM Series Variable Speed AC Motor Drive
Input Voltage:
0 = 120 Vac (For 110, 115, and 120 Vac; 50 or 60 Hz)
2 = 208/240 Vac (For 208, 220, 230, and 240 Vac; 50 or 60 Hz)
4 = 400/480 Vac (For 380, 415, 460, and 480 Vac; 50 or 60 Hz)
Rating:
4 = 0.33 Hp (0.25 kW)
15 = 1.5 Hp (1.1 kW)
75 = 7.5 Hp (5.5 kW)
5 = 0.50 Hp (0.37 kW)
20 = 2 Hp (1.5 kW)
100 = 10 Hp (7.5 kW)
8 = 0.75 Hp (0.55 kW)
30 = 3 Hp (2.2 kW)
150 = 15 Hp (11 kW)
10 = 1 Hp (0.75 kW)
50 = 5 Hp (4.0 kW)
Input Phase:
S = Single phase input only.
No character indicates three phase input only
2.3
SCL/SCM Specifications
Conformity
CE
Low Voltage Directive (2006/95/EC)
Approvals
UL 508C
Underwriters Laboratories - Power Conversion Equipment
Storage Temperature
-20° to 70° C
Ambient Operating Temperature
0° to 40° C (derate 2.5% per °C above 40°)
Ambient Humidity
< 95% (non-condensing)
Altitude
3300 ft (1000 m) above sea level (derate 5% per additional 3300 ft)
Input Line Voltages
120, 208/240, 400/480 Vac
Input Voltage Tolerance
+10%, -15%
Input Frequency Tolerance
48 to 62 Hz
Output Wave Form
Sine Coded PWM
Output Frequency
0 - 240 Hz
Carrier Frequency
4 kHz to 10 kHz (10 kHz requires derating; see parameter P02)
Service Factor
1.00 (up to 8 kHz carrier; derate for 10 kHz; see parameter P02)
Efficiency
Up to 98%
Power Factor (displacement)
0.96 or better
Overload Current Capacity
150% for 60 seconds, 180% for 30 seconds
Speed Reference Follower
0-10 VDC, 4-20 mA
Digital Outputs
(1) Normally open relay; contacts rated 3 amps at 250 Vac
(1) Digital output (current-sourcing); rated 50 mA at 12 VDC
Earth Leakage Current (EN 50178)
SCL: > 3.5 mA to PE SCM: < 3.5 mA to PE