Lenze 13466147 EDBSM01 v19 EN

  

47

Commissioning 4

P55 

0-10 VDC INPUT

Parameter P55 displays the level of the 0-10 VDC input signal at TB-5. A reading of 100% indicates 

a 10 VDC input at TB-5.

P56 

4-20 mA INPUT

Parameter P56 displays the level of the 4-20 mA input signal at TB-25. A reading of 20% indicates a 
4 mA input at TB-25, and a reading of 100% indicates a 20 mA input at TB-25.

P57 

TERMINAL STRIP STATUS

P57 indicates the status of several terminals using the vertical segments of the LED display.  An 
illuminated segment indicates that the particular terminal is closed to TB-11.

FACTORY
RESERVED

TB-1

TB-13A

TB-13B

TB-13E
(output)

TB-13E
(input)

P58 

KEYPAD AND PROTECTION STATUS

P58 indicates the status of the buttons on the keypad, and the status of the protective circuitry 
in the drive, using the horizontal segments of the LED. An illuminated segment indicates that the 
corresponding button is pressed, or the protective circuit is active.

FCLIM

Mode

OUTPUT

FAULT

p

q

FCLIM is an abbreviation for Fast Current Limit.

Содержание SL204S

Страница 1: ...SCL SCM Frequency Inverter Operating Instructions EN 13466147...

Страница 2: ...g but not limited to the implied warranties of it s merchantability and fitness for a given purpose Lenze AC Tech Corporation assumes no responsibility for any errors that may appear in this manual Al...

Страница 3: ...g 18 3 5 1 Control Wiring vs Power Wiring 18 3 5 2 TB 2 Circuit Common 18 3 5 3 Surge Suppression on Relays 18 3 5 4 Start Stop Control 18 3 5 5 Speed Reference Signals 18 3 5 6 Speed Reference Select...

Страница 4: ...as factory If under normal use an SCL SCM motor control becomes defective within the stated warranty time period contact the Lenze Americas Service Department for instructions on obtaining a warranty...

Страница 5: ...trical voltage DANGER Warns of impending danger Consequences if disregarded Death or severe injuries Warning of a general danger WARNING Warns of potential very hazardous situations Consequences if di...

Страница 6: ...out installation in compliance with EMC shielding grounding filters and cables These notes must also be observed for CE marked controllers The manufacturer of the system or machine is responsible for...

Страница 7: ...ondensateurs restent sous charge pendant environ 180 secondes apr s une coupure de courant Couper l alimentation et patienter pendant au moins 3 minutes avant de toucher l entra nement WARNING The ope...

Страница 8: ...74 3 26 83 0 28 7 4 37 111 208 240 3 SM205 N A 5 75 146 2 88 74 3 26 83 0 28 7 4 37 111 400 480 3 SM405 N A 5 75 146 2 88 74 3 94 100 0 80 20 4 37 111 0 75 0 55 208 240 1 SM208S SL208S 5 75 146 2 88...

Страница 9: ...5 75 146 3 76 95 5 53 140 2 18 55 4 37 111 208 240 3 SM230 N A 5 75 146 3 76 95 5 53 140 2 18 55 4 37 111 400 480 3 SM430 N A 5 75 146 3 76 95 5 47 139 2 13 54 4 37 111 5 4 0 208 240 3 SM250 N A 5 75...

Страница 10: ...cations Conformity CE Low Voltage Directive 2006 95 EC Approvals UL 508C Underwriters Laboratories Power Conversion Equipment Storage Temperature 20 to 70 C Ambient Operating Temperature 0 to 40 C der...

Страница 11: ...L215S 1 5 1 1 1 13 9 12 0 2 9 6 9 6 0 68 SM215 N A 1 5 1 1 3 8 0 6 9 2 9 6 9 6 0 68 SM220S SL220S 2 1 5 1 18 4 16 0 3 1 8 1 7 0 71 SM220 N A 2 1 5 3 9 1 7 9 3 3 8 1 7 0 71 SM230S SL230S 3 2 2 1 24 21...

Страница 12: ...drives or heat producing equipment Fans or blowers should be used to insure proper cooling in tight quarters In order to properly size an enclosure the heat generated by the drive s must be known Refe...

Страница 13: ...phase voltage imbalance must be less than 2 0 phase to phase Excessive phase to phase imbalance can cause severe damage to the drive Motor voltage should match line voltage in normal applications The...

Страница 14: ...Select fuses with low I2 T values rated at 200 000 AIC Recommended fuses are Bussman KTK R JJN and JJS Similar fuses with equivalent ratings by other manufacturers may also be acceptable Per UL Requir...

Страница 15: ...nal installation in its entirety not to the individual components used Because every installation is different the recommended installation should follow these guidelines as a minimum Additional equip...

Страница 16: ...ntactor more than once every two minutes may cause damage to the drive 3 3 1 Input and Output Wiring On single phase input models wire the input power to terminals L1 and L2 N On three phase input mod...

Страница 17: ...r to output terminals U V W or terminals B B Severe damage to the drive will result Leakage current may exceed 3 5 mA AC Minimum size of the protective earth PE conductor shall comply with local safet...

Страница 18: ...ommon for the analog speed reference inputs If necessaryTB 2 may be connected to chassis ground 3 5 3 Surge Suppression on Relays Current andvoltagesurgesandspikesinthecoilsofcontactors relays solenoi...

Страница 19: ...ted by different combinations of contact closures between TB 13A 13B 13E and TB 11 Refer to Parameters 31 37 in Section 4 4 Description of Parameters JOG TB 13B can be programmed to select either JOG...

Страница 20: ...TB 13A is closed to TB 11 TB 13A will override the MOP function 3 5 7 Drive Status Digital Outputs There is one Form A relay at terminalsTB 16 andTB 17 The relay contacts are rated 3 amps at 250Vac Te...

Страница 21: ...COMMON 0 10V DC INPUT TB 13A FUNCTION SELECT TB 13B FUNCTION SELECT TB 13E FUNCTION SELECT 4 20mA INPUT FORM A RELAY SPEED POT POWER SUPPLY DIGITAL INPUT REFERENCE SCL SCM Terminal Strip NOTE The func...

Страница 22: ...act REVERSE RUN REVERSE 2 Wire Start Stop Control NOTE Close TB 1 to TB 11 to RUN and open to STOP TB 1 functions as a RUN input for two wire start stop circuits and a STOP input for three wire start...

Страница 23: ...t START REVERSE REV FWD START FORWARD 3 Wire Start Stop Control NOTE Program TB 13E Parameter 12 for START FORWARD 06 If reverse direction is required set ROTATION Parameter 17 to FORWARD AND REVERSE...

Страница 24: ...D 2 PRESET SPEED 3 SPEED POT Speed Potentiometer NOTE For preset speed control all or some of the TB 13 terminals must be programmed as preset speed selects If only two or three preset speeds are requ...

Страница 25: ...shown below Apply input power Display then reads Display flashes parameter version 300 399 Follow this 4 step procedure to check the motor rotation This procedure assumes that the drive has been powe...

Страница 26: ...he drive output terminals or at the motor 4 2 Programming the SCL SCM Drive The drive may be programmed by one of two methods using the three buttons and 3 digit LED display on the front of the drive...

Страница 27: ...ed the display will read P01 which indicates that the PROGRAM mode has been accessed at the beginning of the parameter menu P01 is the first parameter This is shown below Press Mode to enter password...

Страница 28: ...the password is not required access the parameters Aftertwominutes thepasswordmust beenteredinordertoaccesstheparametersagain 4 2 1 Setting Values in Tenths of Units Above 100 Parameter settings and t...

Страница 29: ...seconds Go to Parameter 19 and press Mode to see present setting 243 seconds Upper right decimal point blinks Press p button to see tenths portion Upper right decimal point and lower decimal point bli...

Страница 30: ...not remove the EPM while power is applied to the drive Damage to the EPM and or drive may result The optional EPM Programmer has the ability to quickly and easily program many SC Series drives for the...

Страница 31: ...01 05 STANDARD SPEED SOURCE KEYPAD 01 PRESET 1 02 0 10 VDC 03 4 20 mA 04 KEYPAD 01 06 RELAY OUTPUT NONE 01 RUN 02 FAULT 03 INVERSE FAULT 04 FAULT LOCKOUT 05 AT SET SPEED 06 ABOVE PRESET 3 07 CURRENT...

Страница 32: ...4 CONTROL TERMINAL STRIP ONLY 01 REMOTE KEYPAD ONLY 02 TERMINAL STRIP ONLY 01 16 UNITS EDITING TENTHS OF UNITS 01 WHOLE UNITS 02 WHOLE UNITS 02 17 ROTATION FORWARD ONLY 01 FORWARD AND REVERSE 02 FORWA...

Страница 33: ...SPEED AT MIN SIGNAL MINIMUM FREQUENCY 999Hz 0 0Hz 46 SPEED AT MAX SIGNAL MINIMUM FREQUENCY 999Hz SCL 50 Hz SCM 60 Hz 47 CLEAR HISTORY MAINTAIN 01 CLEAR 02 MAINTAIN 01 48 PROGRAM SELECTION USER SETTIN...

Страница 34: ...CL SCM drive is fully rated up to 8 kHz carrier frequency If the 10 kHz carrier frequency is selected the drive s ambient temperature rating OR output current rating must be de rated to the value show...

Страница 35: ...inning load after a fault or upon application of input power They differ in the time required to find the motor speed and the amount of current required to synchronize with it The faster the drive att...

Страница 36: ...e 03 FAULT Closes if there is no fault condition Opens if the drive faults or input power is removed 04 INVERSE FAULT Closes if the drive faults Opens if there is no fault condition 05 FAULT LOCKOUT C...

Страница 37: ...LT Sets TB 13A as a normally closed external fault input Open TB 13A to TB 11 to trip the drive 09 INVERSE EXTERNAL FAULT Sets TB 13A as a normally open external fault input Close TB 13A to TB 11 to t...

Страница 38: ...time programmed into Parameter 42 ACCEL DECEL 2 13 REMOTE KEYPAD When the Remote Keypad option is being used TB 13B must be set to this function Also TB 13E Parameter 12 must be set for REMOTE KEYPAD...

Страница 39: ...a STOP state the drive faults or input power is removed DC braking is considered a STOP state 12 FAULT Closes if there is no fault condition Opens if the drive faults or input power is removed 13 INVE...

Страница 40: ...nits until 99 9 is reached Above 99 9 the value will change in whole unit increments only Below a value of 100 if the p or q button is pressed and held the value will change by tenths of units until t...

Страница 41: ...erate the load If RAMP WITH DC BRAKE is selected braking is activated when the output frequency reaches 0 2 Hz In this case the drive decelerates the load to a near stop and then DC braking is used to...

Страница 42: ...UENCY determines the V Hz ratio by setting the output frequency at which the drive will output full voltage to the motor In most cases the BASE FREQUENCY should be set to match the motor s rated frequ...

Страница 43: ...CLOSED OPEN 3 OPEN OPEN CLOSED 4 CLOSED CLOSED OPEN 5 CLOSED OPEN CLOSED 6 OPEN CLOSED CLOSED 7 CLOSED CLOSED CLOSED NOTE When a TB 13 terminal is programmed for a function other than a preset speed...

Страница 44: ...le A machine produces 175 parts per hour when the motor is running at 60 Hz Setting SPEED SCALINGto175willcalibratethedrive sdisplaytoread175whenthemotorisrunningat 60Hz Thisis alinearfunction soat 30...

Страница 45: ...OEM default settings which configure the drive for a specific application When operating in OEM mode the parameter values can be viewed but not changed If an attempt is made to change a parameter set...

Страница 46: ...elasteightfaultsthattrippedthedrive RefertoSection5 Troubleshooting for a list of the faults and possible causes Use the p and q buttons to scroll through the fault entries The faults are stored from...

Страница 47: ...57 indicates the status of several terminals using the vertical segments of the LED display An illuminated segment indicates that the particular terminal is closed to TB 11 FACTORY RESERVED TB 1 TB 13...

Страница 48: ...r 60 Once the desired parameter is found press the Mode button to view its contents When finished press Mode to exit the parameter menu An example is shown herein Press Mode once Upper right decimal p...

Страница 49: ...oltage Fault Line voltage is too low OF Output Transistor Fault Phase to phase or phase to ground short circuit on the output Boost settings are too high Acceleration rate is too fast Failed output tr...

Страница 50: ...ew speed Once the actual speed reaches the commanded speed the upper left decimal point will turn on solid for 5 seconds and then turn off to indicate that the commanded speed has been reached and tha...

Страница 51: ...s made to change parameter settings without performing the TRANSLATE function Refer to PROGRAM SELECTION Parameter 48 CL CURRENT LIMIT The output current has exceeded the CURRENT LIMIT setting Paramet...

Страница 52: ...et Uxbridge MA 01569 USA 800 217 9100 508 278 7873 marketing lenzeamericas com www Lenze com Service Lenze AC Tech Corporation 630 Douglas Street Uxbridge MA 01569 USA 508 278 9100 508 278 6620 repair...

Отзывы: