4 Commissioning
P05
STANDARD SPEED SOURCE
P05 selects the speed reference source when the drive is in STANDARD speed mode. The following
speed references can be selected:
01
KEYPAD: Use the
p
and
q
buttons to scroll to the desired speed.
02
PRESET SPEED #1: Drive will operate at the frequency set in Parameter 31.
03
0-10 VDC: Drive will respond to a 0-10 VDC signal wired to TB-5 (+) and TB-2 (-).
04
4-20 mA: Drive will respond to a 4-20 mA signal wired to TB-25 (+) and TB-2 (-).
P06
RELAY OUTPUT
P06 selects the status indication for the normally open relay output at TB-16 and TB-17:
01
NONE: Disables the relay output.
02
RUN: Closes upon a START command. Opens if the drive is in a STOP state, the drive faults, or
input power is removed. DC braking is considered a STOP state.
03
FAULT: Closes if there is no fault condition. Opens if the drive faults, or input power is removed.
04
INVERSE FAULT: Closes if the drive faults. Opens if there is no fault condition.
05
FAULT LOCKOUT: Closes when input power is applied. Opens if three restart attempts are
unsuccessful, or if input power is removed.
06
AT SET SPEED: Closes if the drive is 0.5 Hz of the speed setpoint.
07
ABOVE PRESET SPEED #3: Closes if the output frequency exceeds PRESET SPEED #3 (Parameter
33). Opens if the output frequency is equal to or less than PRESET SPEED #3.
08
CURRENT LIMIT: Closes if the output current exceeds the CURRENT LIMIT setting. Opens if the
output current is equal to or less than CURRENT LIMIT (see Parameter 25).
09
AUTOMATIC SPEED MODE: Closes if an AUTOMATIC (terminal strip) speed reference is active.
Opens if a STANDARD (Parameter 5) speed reference is active.
10
REVERSE: Closes when reverse rotation is active. Opens when forward rotation is active (see
Parameter 17 - ROTATION DIRECTION).