Appendix
Code table
l
89
LDEDS−CCU210B EN 4.0
Description
Possible settings
Code
Selection
Lenze
Byte
<
ñò
No.
C0018
Switching frequency of the inverter
in ...
^
1 RW
EXT
4
2
8 kHz
... Parameter set 1
2
2
8 kHz
... Parameter set 2
Possible values
0
2 kHz
1
4 kHz
2
8 kHz
C0019
Operating threshold for automatic
brake in ...
1 RW
EXT
4
0
0
{Hz}
20 ... Parameter set 1
2
0
... Parameter set 2
C0022
Rated motor current in ...
^
1 RW
EXT
4
1.0
0
{A}
20.0 ... Parameter set 1
2
1.0
... Parameter set 2
C0024
V/f characteristic – U-boost voltage
in ...
^
1 RW
EXT
4
5.0
1
{%}
25.5 ... Parameter set 1
2
5.0
... Parameter set 2
C0029
V/f characteristic – base frequency
in ...
^
1 RW
EXT
4
50.0
0
{Hz}
120.0 ... Parameter set 1
2
50.0
... Parameter set 2
C0040
RW
4
0
Controller inhibit
0
Controller inhibited
1
Controller enabled
C0043
RW
4
0
Acknowledge fault
0
Action executed
1
Acknowledge fault
C0050
R
4
Current drive frequency
^
0
{Hz}
120.0
C0053
R
4
Current DC−bus voltage
^
0
{V}
1000
C0054
R
4
Current motor current
^
0
{A}
20.0
C0056
R
4
Current output stage temperature
^
0
{°C}
255
C0089
R
4
Frequency inverter − software
version
C0093
R
4
Device type
C0099
R
4
Software version
{xy}
x = main version, y = subversion
C0118
RW
INT
1
10
Configuration of brake resistance
monitoring (WR only with PWD)
10
Resistance 200
W
/100 W
30
Resistance 150
W
/300 W
Содержание LDEC Series
Страница 2: ...0Fig 0Tab 0 ...
Страница 24: ...Mechanical installation Dimensions 5 l 24 LDEDS CCU210B EN 4 0 5 2 Dimensions Power 0 75 kW CCU210_002H ...
Страница 25: ...Mechanical installation Dimensions 5 l 25 LDEDS CCU210B EN 4 0 Power 1 5 kW CCU210_002B ...
Страница 26: ...Mechanical installation Dimensions 5 l 26 LDEDS CCU210B EN 4 0 Power 2 2 kW CCU210_002_2_2kW ...