Technical data
Rated data
l
22
LDEDS−CCU210B EN 4.0
Half wave system
Control bar
Z system
No
Number
2
Signal level
Full wave
Positive half wave
Negative half wave
Reference voltage or switched
voltage
L3
L1 possible with different hardware configuration
Rated voltage
400 ... 480 V AC,
50−60 Hz
Switching threshold
50 Hz: 270 V AC (243 ... 297 V AC)
60 Hz: 330 V AC (297 ... 363 V AC)
Power consumption
1.5 W (400 V AC)
for 1 x half wave
Message bar
Number
1
Signal level
Full wave
Positive half wave
Negative half wave
Reference voltage or switched
voltage
L3
L1 possible with different hardware configuration
Short−circuit protection
PTC protection (500
W
in series)
Reference voltage
400 ... 480 V
Switching current
max. 28 mA AC
Sensor technology
Digital inputs
Number
8
Level
HIGH
+16 . +26.5 V DC
LOW
0 . 4 V DC
Input current
Typ. 4 mA at 24 V DC
Digital outputs
Number
2
Level
HIGH
+19 . +26.4 V DC
LOW
0 . 4 V DC
Output current
Max. 200 mA per
output
If inductive loads are switched,
external freewheeling diodes are
required!
Serial interface
RS485
SensoPart protocol
Parameter setting and configuration
IrDA interface
Serial IrDA interface for parameter setting
Range typ. 300 mm
CAN interface
For parameter setting and configuration
Manual control
IR−RC interface
Manual operation using infrared remote control
External data memory
Storage space
Max. 2 kB
Depending on the application