Troubleshooting and fault elimination
820XBA1097
8-3
8.3 Fault indications
Display
Fault
Cause
Remedy
---
No fault
-
-
EEr
External fault (TRIP-Set)
A digital input assigned to the
TRIP-Set function has been
activated
Check external encoder
H05
Internal fault
Contact Lenze
LU
Undervoltage
DC-bus voltage too low
-
Check mains voltage
-
Check supply module
OC1
Short circuit
Short circuit
Find out cause of short circuit; check
cable
Excessive capacitive charging
current of the motor cable
Use motor cable which is shorter or of
lower capacitance
OC2
Earth fault
Grounded motor phase
Check motor; check cable
OC2
Earth fault
Excessive capacitive charging
current of the motor cable
Use motor cable which is shorter or of
lower capacitance
OC3
Overload inverter during
acceleration or short
circuit
Acceleration time too short
(C012)
-
Increase acceleration time
-
Check drive selection
acceleration or short
circuit
Defective motor cable
Check wiring
Interturn fault in the motor
Check motor
OC4
Overload controller during
deceleration
Deceleration time too short
(C013)
-
Increase deceleration time
-
Check the selection of the brake
resistor or connect the brake
chopper
OC5
I x t overload
Frequent and too long
acceleration processes with
overcurrent
Check drive dimensioning
Permanent overload with
I
motor
> 1.05 x I
Nx
OC6
Overload motor
Motor is thermally overloaded, for
instance, because of
-
impermissible continuous
current
-
Check drive selection
-
frequent or too long
acceleration processes
-
Check the setting under C120