![Lenze EVF8201-E Скачать руководство пользователя страница 53](http://html1.mh-extra.com/html/lenze/evf8201-e/evf8201-e_operating-instructions-manual_1882342053.webp)
Configuration
820XBA1097
7-5
Code
IMPORTANT
Possible settings
Name
Code
IMPORTANT
Info
Selection
Lenze
Name
C009* Device address
1
1
{1}
99
Only for
LECOM
applications
C010 Minimum field
frequency
0.0
0.0
{0.1Hz}
480.0
C011 Maximum field
frequency
820X
50.0
30.0
{0.1Hz}
480.0
821X
50.0
7.5
{0.1Hz}
480.0
30.0
{0.1Hz}
480.0
(Software 2x)
(Software 1x)
822X/824X
50.0
7.5
{0.1Hz}
480.0
C012 Acceleration
time
5.0
0.0
{0.1s}
999.0
C013 Deceleration
time
5.0
0.0
{0.1s}
999.0
C014
§
Operating mode
820X
-0-
-0-
Linear characteristic V
f
d
with auto
boost
-1-
Square characteristic V
f
d
2
with auto
boost
-2-
Linear characteristic V
f
d
with constant
V
min
boost
-3-
Square characteristic V
f
d
2
with
constant V
min
boost
821X/822X
/ 824X
-4-
-4-
Motor-current control
C015 V/f-rated
frequency
820X
50.0
30.0
{0.1Hz}
960.0
821X
50.0
7.5
{0.1Hz}
960.0
30.0
{0.1Hz}
960.0
(Software 2x)
(Software 1x)
822X/824X
50.0
7.5
{0.1Hz}
960.0