![Lenze EVF8201-E Скачать руководство пользователя страница 46](http://html1.mh-extra.com/html/lenze/evf8201-e/evf8201-e_operating-instructions-manual_1882342046.webp)
Commissioning
5-14
820XBA1097
3. Set the Vmin boost
(C016).
-
Load-independentboost of the motor voltage for field frequencies below the
U/f-rated frequency. You can thus optimize the torque performance of the inverter
drive.
-
It is absolutely necessary to adapt the asynchronous motor used, since otherwise,
the motor can be destroyed by overtemperatue:
Adjustment
Please note the thermal characteristic of the connected motor under small field
frequencies:
-
Usually, standard asynchronous motors with insulation class B can be operated for a
short time with rated current and frequencies between 0Hz
$
f
d
$
25Hz.
-
Please ask the motor manufacturer for the exact setting values for the motor
current.
A Operate the motor in idle running with a slip frequency of f
d
:
- P
mot
$
7.5 kW: f
d
5 Hz
- P
mot
7.5 kW: f
d
2 Hz
B Increase V
min
until you reach the following motor current:
- Motor in short-term operation at 0Hz
$
f
d
$
25Hz:
with self-ventilated motors:
I
motor
$
I
N motor
with forced-ventilated motors:
I
motor
$
I
N motor
- Motor in permanent operation at 0Hz
$
f
d
$
25Hz:
with self-ventilated motors
I
motor
$
0.8
k
I
N motor
with forced-ventilated motors:
I
motor
$
I
N motor
4. Set slip compensation
(C021).
Rough setting by means of the motor data:
4. Set slip compensation
(C021).
s
n
rsyn
n
r
n
rsyn
ô
100%
n
rsyn
f
dr
ô
60
p
s
Slip constant (C021)
n
rsyn
synchronous motor speed [min
-1
]
n
r
rated speed to motor nameplate [min
-1
]
f
dr
rated frequency to motor nameplate [Hz]
p
Number of pole pairs
Precise setting:
Change C021 under constant load until the speed is near the synchronous speed.
If C021 is set to too high values, the drive may become instable (overcompensation).
All manuals and user guides at all-guides.com
all-guides.com