Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 3.0 - 02/2019
135
Implemented CIP™ objects
"AC Drive Profile" objects
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
14.3.2
Control Supervisor Object (41 / 0x29)
The "Control Supervisor Object" describes all management functions of the devices used to control
the motor.
Class attributes
Instance attributes
Attribute
ID
Service
Name
Data type
Value
1
Get
Revision
UINT
1 (0x0001)
2
Get
Max. Instance
UINT
1 (0x0001)
3
Get
Number of Instances
UINT
1 (0x0001)
Attribute
ID
Service
Name
Data type
Value
1
Get
NumAttr
USINT
Number of supported attributes
2
Get
Attributes
ARRAY of
USINT
Listing of the supported attributes
3
Set
Run1
BOOL
Run/stop can be controlled via a local setting
on the device or terminal, or via the network
(see attribute "NetCtrl").
The relationship between Run1, Run2 and
the trigger events is described in the
4
Set
Run2
BOOL
5
Set
NetCtrl
BOOL
Run/Stop control
• 0: Run/stop control via local setting on
the device or terminal
• 1: Run/stop control via network (e.g. from
the scanner)
6
Get
State
USINT
• 0: Manufacturer-specific
• 1: Startup
• 2: Not_Ready
• 3: Ready
• 4: Enabled
• 5: Stopping
• 6: Fault_Stop
• 7: Faulted
7
Get
Running1
BOOL
• 0: Other status than listed under ’1’
• 1: [Enabled and Run1] or
[Stopping and Running1] or
[Fault_Stop and Running1]
8
Get
Running2
BOOL
• 0: Other status than listed under ’1’
• 1: [Enabled and Run2] or
[Stopping and Running2] or
[Fault_Stop and Running2]
9
Get
Ready
BOOL
• 0: Other status than listed under ’1’
• 1: Ready or Enabled or Stopping
10
Get
Faulted
BOOL
• 0: No errors
• 1: Errors have occurred
11
Get
Warning
BOOL
• 0: No warnings
• 1: Warnings have occurred
12
Set
FaultRst
BOOL
• 0
1: Reset error
• 0: No Response