Implemented CIP™ objects
EtherNet/IP objects
124
Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 3.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
14.2.2
Quality of Service (QoS) Object (72 / 0x48)
The "Quality of Service (QoS) Object" enables different classifications and prioritisations of the data
packets for EtherNet/IP communication. For this purpose, the EtherNet/IP messages are marked
with "802.1Q tags" and "Differentiated Services Codepoints" (DSCP).
Class attributes
Instance attributes
The instance attributes act independently of each other.
The DSCP values are used for the IP headers.
Irrespective of this, VLAN tagging can be activated in addition (
= 1).
The VLAN ID of Lenze devices is ’0’.
The VLAN priority results from the DSCP values configured.
Changes in the attribute values will only take effect after a reset of the device ("power off/on" or
"type 0 reset").
Attribute
ID
Service
Name
Data type
Value
1
Get
Revision
UINT
1 (0x0001)
2
Get
Max. Instance
UINT
1 (0x0001)
3
Get
Number of Instances
UINT
1 (0x0001)
6
Get
Max. ID Number Class
Attributes
UINT
7 (0x0007)
7
Get
Max. ID Number Instance
Attributes
UINT
8 (0x0008)
Note!
Before activating VLAN tagging, please ensure that all involved components support
VLAN tagging. It may occur that the devices not supporting VLAN tagging cannot be
accessed anymore.
Attribute
ID
Service
Name
Data type
Value
1
Set
802.1Q Tag Enable
USINT
Enables the sending of data packets with
802.1Q tags (
• 0: No use of 802.1Q tags (Lenze setting
)
• 1: Use of 802.1Q tags
4
Set
DSCP Urgent
USINT
55: Urgent/imperative messages
Is not supported at the moment.
5
Set
DSCP Scheduled
USINT
47: Scheduled messages
(Can only be used for "exclusive owner"
connections.)
)
6
Set
DSCP High
USINT
43: Messages with high priority
(Can only be used for "input only" and "listen