Error messages
Possible causes and remedies
86
Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 3.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
EtherNet/IP: Idle Mode [0x01bc8132] (nt05: COM fault 5)
EtherNet/IP: Duplicate IP Address [0x01bc8273]
Response
(Lenze setting printed in bold)
Setting:
No reaction
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
Warning
Information
Cause
Remedy
• Scanner has received an idle event.
• The scanner is in the "PROG" mode.
• In the "Scanner Command Register", the run/
idle flag (bit 0) is 0.
Set the scanner to the run mode.
Run/idle flag (bit 0) = 1
Response
(Lenze setting printed in bold)
Setting:
not possible
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
warning
Information
Cause
Remedy
An IP address has been allocated twice within the
network. The addresses of the network nodes must differ
from each other.
Correct the IP address (
).