RG-MHBAC

Drive Setup & Programming

57 SERIAL 

This parameter needs to be set to either WITH TIMER (default) or W/O TIMER for 
the drive to communicate with the LAN. Serial communications will not work if this 
parameter is set to DISABLED.

58 MAC ADDRESS 

This parameter contains the address of the MCH drive. It is adjustable from 0-254 
and has a factory default value of 128.

60 SERIAL TIMEOUT  This  parameter  makes  the  serial  watchdog  timeout  period  selectable.  It  has  a 

minimum value of 10 seconds and maximum value of 65535 seconds. The default is 
30 seconds. If no action is to be taken when a serial watchdog timeout occurs, Drive 
Parameter #57 (Serial) should be set to W/O TIMER. This will disable the watchdog 
timer. Otherwise Drive Parameter #57 (Serial) should be set to WITH TIMER.

If the LAN has started the drive or has modified the Speed Source Selection (MV1), 
the Keypad Speed Command (AV1) or the Keypad Setpoint Command (AV2) and a 
serial watchdog timeout occurs, the drive is taken out of serial control.

If Drive Parameter #30 (Control) is set to SERIAL AUTO and the drive was running 
when  the  timeout  occurred,  the  drive  will  also  stop  the  motor  by  tripping  into  a 
SERIAL FAULT. A fault reset command, issued via Clear Fault (BV1), a keypad stop 
or a terminal stop is required to clear the fault.

If Drive Parameter #30 (Control) is set to SERIAL SPEED, then the action to be taken 
when a timeout occurs is determined by Drive Parameter #56 (Serial Loss).

When Drive Parameter #30 (Control) is set to SERIAL SPEED the speed reference 
being used MUST be set to the drive keypad (-KEY, -MKB, -AKB) or the LAN (-SER) 
for the serial watchdog to be active. When Drive Parameter #30 is set to SERIAL 
AUTO the serial watchdog will be active with any speed reference.

Also,  if  the  LAN  has  written  to  the  keypad  speed  command,  the  speed  source 
changes from keypad to serial and the keypad speed command cannot be changed 
using the drive keypad. In order for the drive keypad to take control of the keypad 
speed command, the drive H/O/A must be toggled to HAND or OFF to release serial 
control  of  the  corresponding  BACnet®  object.  The  same  is  true  of  the  keypad 
setpoint command and the speed source selection.

Содержание AC Tech MCH Series

Страница 1: ...MCH Series Drives BACnet Communications Guide...

Страница 2: ...nc 1791 Tullie Circle NE Atlanta GA 30329 http www bacnet org Modbus is a registered trademark of Schneider Electric founder of Modbus IDA http www modbus IDA org 2003 AC Technology Corporation No par...

Страница 3: ...ed Programming Parameters 4 3 2 Omitted Parameters and Selections 4 3 3 Modified Parameters and Selections 5 3 4 Serial Communication Setup 5 4 MCH BACnet Objects 8 4 1 BACnet Object Map 8 4 2 Analog...

Страница 4: ...n installing the drive controllers in machines commissioning i e the starting of operation as directed is prohibited until it is proven that the machine complies with the regulations of the EC Directi...

Страница 5: ...adapt the controller to your application as described in the documentation DANGER After the controller has been disconnected from the supply voltage do not touch the live components and power connect...

Страница 6: ...length of an MS TP segment is 1200 meters 4000 feet with AWG 18 cable Maximum number of nodes unit loads per segment is 32 as specified by the EIA 485 standard Because MS TP uses non return to zero N...

Страница 7: ...e of bits 0 15 of the drive s 22 bit device number It can be used by itself to represent a device number in the range of 0 to 65535 If the device number exceeds 65535 then DEVICE NUM EX must also be u...

Страница 8: ...ng of all MCH BACnet points Write commands will not be accepted without proper modification to these drive settings One exception to this is STOP commands which are always accepted over the LAN For se...

Страница 9: ...erial watchdog timeout occurrence The options for this parameter are FAULT default and PRESET 3 If FAULT is selected and the drive is running when a serial watchdog timeout occurs the drive will trip...

Страница 10: ...of serial control If Drive Parameter 30 Control is set to SERIAL AUTO and the drive was running when the timeout occurred the drive will also stop the motor by tripping into a SERIAL FAULT A fault res...

Страница 11: ...ommand PID SETPOINT 1 00 50 AI 7 PID Feedback PID FEEDBACK 1 00 0 AV 1 Keypad Speed Command KEY SPD CMD Hz 0 01 20 00 AV 2 Keypad Setpoint Command KEY STPT CMD 1 00 50 BI 1 Run Stop Status RUN_STOP 1...

Страница 12: ...back This object is for monitoring the current PID Feedback value at the input specified by Drive Parameter 74 PID Feedback The range of this object is defined by Drive Parameter 75 Feedback Min and D...

Страница 13: ...information Object BI 6 Relay 1 This object monitors the state of the drive s Relay 1 output This object can be used to indicate various drive conditions as specified by Drive Parameter 54 RELAY1 Ref...

Страница 14: ...his object indicates the type of fault on which the drive is currently tripped This object returns a value between 1 and 25 which corresponds to one of the following fault conditions Value Name Fault...

Страница 15: ...is for monitoring the source of the speed setpoint reference States 1 through 9 are speed references States 10 through 18 are setpoint references This object must be in state 1 9 or 10 for the LAN to...

Страница 16: ...peed Source Selection This object mimics the functionality of the SPEED SOURCE key on the drive keypad It is used to determine whether the drive will get its speed setpoint reference from Drive Parame...

Страница 17: ...AC Technology Corporation 630 Douglas Street Uxbridge MA 01569 USA Sales 800 217 9100 Service 508 278 9100 www lenze actech com RG MHBAC e2...

Отзывы: