RG-MHBAC 

12

BACnet Objects

Object MSI-3:  PID Mode
 

This object is for monitoring the general state of the drive’s PID mode as specified by Drive 
Parameter #70 (PID Mode).

State

Name

PID Control

1

OFF

PID disabled.

2

NORMAL

Enable direct-acting system (INC FDBK, DEC MTR SPD)

3

REVERSE

Enable reverse-acting system (INC FDBK, INC MTR SPD)

Object MSI-4:  H/O/A Mode
 

This object is for monitoring the drive H/O/A status. If the drive H/O/A is OFF (1) or HAND 
(2), serial speed/setpoint and serial start commands will not be accepted from the LAN. 
If the drive H/O/A is AUTO (3), depending on the setting of Drive Parameter #30 (Control), 
serial speed/setpoint and serial start commands will be accepted. For more information, 
refer to Section 3.4.

State

Name

Accept Serial Command?

Speed/Setpoint

Start

1

OFF

No

No

2

HAND

No

No

3

AUTO

Parameter 30 setting

Parameter 30 setting

Object MSI-5:  Speed/Setpoint Reference
 

This object is for monitoring the source of the speed/setpoint reference. States 1 through 
9 are speed references. States 10 through 18 are setpoint references. This object must be 
in state 1, 9 or 10 for the LAN to be able to command the drive speed. This object must be 
in state 11 or 19 for the LAN to be able to command the drive setpoint. The state test table 
for this point is as follows:

State

Name Description

Reference

1

-KEY

Keypad Speed Command

(Open loop speed control - PID Disabled)

2

-VDC

0-10 VDC on TB-5A

(Open loop speed control - PID Disabled)

3

-IDC

4-20 mA on TB-5B

(Open loop speed control - PID Disabled)

4

SP#1

Preset Speed #1

(Open loop speed control - PID Disabled)

5

SP#2

Preset Speed #2

(Open loop speed control - PID Disabled)

6

SP#3

Preset Speed #3

(Open loop speed control - PID Disabled)

7

SP#4

Preset Speed #4

(Open loop speed control - PID Disabled

8

-MOP

Motor Operated Pot

(Open loop speed control - PID Disabled)

9

-SER

Serial Speed Command

(Open loop speed control - PID Disabled)

10

-MKB

Keypad Speed Command

(Open loop speed control - PID Enabled)

11

-AKB

Keypad Setpoint Command

(Closed loop setpoint control - PID Enabled)

Содержание AC Tech MCH Series

Страница 1: ...MCH Series Drives BACnet Communications Guide...

Страница 2: ...nc 1791 Tullie Circle NE Atlanta GA 30329 http www bacnet org Modbus is a registered trademark of Schneider Electric founder of Modbus IDA http www modbus IDA org 2003 AC Technology Corporation No par...

Страница 3: ...ed Programming Parameters 4 3 2 Omitted Parameters and Selections 4 3 3 Modified Parameters and Selections 5 3 4 Serial Communication Setup 5 4 MCH BACnet Objects 8 4 1 BACnet Object Map 8 4 2 Analog...

Страница 4: ...n installing the drive controllers in machines commissioning i e the starting of operation as directed is prohibited until it is proven that the machine complies with the regulations of the EC Directi...

Страница 5: ...adapt the controller to your application as described in the documentation DANGER After the controller has been disconnected from the supply voltage do not touch the live components and power connect...

Страница 6: ...length of an MS TP segment is 1200 meters 4000 feet with AWG 18 cable Maximum number of nodes unit loads per segment is 32 as specified by the EIA 485 standard Because MS TP uses non return to zero N...

Страница 7: ...e of bits 0 15 of the drive s 22 bit device number It can be used by itself to represent a device number in the range of 0 to 65535 If the device number exceeds 65535 then DEVICE NUM EX must also be u...

Страница 8: ...ng of all MCH BACnet points Write commands will not be accepted without proper modification to these drive settings One exception to this is STOP commands which are always accepted over the LAN For se...

Страница 9: ...erial watchdog timeout occurrence The options for this parameter are FAULT default and PRESET 3 If FAULT is selected and the drive is running when a serial watchdog timeout occurs the drive will trip...

Страница 10: ...of serial control If Drive Parameter 30 Control is set to SERIAL AUTO and the drive was running when the timeout occurred the drive will also stop the motor by tripping into a SERIAL FAULT A fault res...

Страница 11: ...ommand PID SETPOINT 1 00 50 AI 7 PID Feedback PID FEEDBACK 1 00 0 AV 1 Keypad Speed Command KEY SPD CMD Hz 0 01 20 00 AV 2 Keypad Setpoint Command KEY STPT CMD 1 00 50 BI 1 Run Stop Status RUN_STOP 1...

Страница 12: ...back This object is for monitoring the current PID Feedback value at the input specified by Drive Parameter 74 PID Feedback The range of this object is defined by Drive Parameter 75 Feedback Min and D...

Страница 13: ...information Object BI 6 Relay 1 This object monitors the state of the drive s Relay 1 output This object can be used to indicate various drive conditions as specified by Drive Parameter 54 RELAY1 Ref...

Страница 14: ...his object indicates the type of fault on which the drive is currently tripped This object returns a value between 1 and 25 which corresponds to one of the following fault conditions Value Name Fault...

Страница 15: ...is for monitoring the source of the speed setpoint reference States 1 through 9 are speed references States 10 through 18 are setpoint references This object must be in state 1 9 or 10 for the LAN to...

Страница 16: ...peed Source Selection This object mimics the functionality of the SPEED SOURCE key on the drive keypad It is used to determine whether the drive will get its speed setpoint reference from Drive Parame...

Страница 17: ...AC Technology Corporation 630 Douglas Street Uxbridge MA 01569 USA Sales 800 217 9100 Service 508 278 9100 www lenze actech com RG MHBAC e2...

Отзывы: