Technical data
3-2
BA2112EN
3.3
Rated data
Field
Values
Communication medium
ASIC LPCII
Supply voltage
Voltage supply via INTERBUS-Loop.
Insulation voltage - bus systems:
•
to PE
50 V AC
•
to external supply (terminal 39/59)
0 V
(no electrical isolation)
•
to power stage
– 820X / 821X
270 V AC
(single basic insulation)
– 822X / 93XX / 8200 vector
270 V AC
(double basic insulation)
•
to the control terminals
– 8200 vector
100 V AC
(single basic insulation)
– 820X
0 V
(no electrical isolation)
– 821X
50 V AC
(electrical isolation)
– 822X / 93XX
270 V AC
(single basic insulation)
•
to external bus system
0 V
(no electrical isolation)
Degree of pollution
VDE 0110 part 2 pollution degree 2
3.4
Dimensions
18
75.2
61.8
INTERBUS loop
2112
IN
OUT
Fig. 3-1
Dimensions of the 2112 fieldbus module
3.5
Protocol data
Field
Values
Maximum number of controllers with InterBus-Loop 2112
36
Process-data words (PCD):
2 words (32 bit)
INTERBUS-Loop identification
179 (decimal) or B3 (hex)
Baud rate
500 kbit/s