![Lenze AC Tech LonWorks MCH Series Скачать руководство пользователя страница 7](http://html.mh-extra.com/html/lenze-ac-tech/lonworks-mch-series/lonworks-mch-series_communications-manual_1882579007.webp)
RG-MHLON
4
Drive Setup & Programming
2.2 LED Status Indicators
LED 1 - Drive Communication
This LED indicates the communication status between the comm module and the drive.
LED State
Indicates:
Steady Green
Link OK
Steady Red
Link lost, permanent
Flashing Red
Link lost, temporary
LED 2 - Service
This LED indicates the node configuration and application status.
LED State
Indicates:
Steady OFF
Node configured and installed in network
Steady Green
Node not configured, has no application; Error detected by Neuron Self Test routine
Flashing Green Node not configured and not installed in network but node has an application
LED 3 - Wink
This LED indicates receipt of a wink command.
LED State
Indicates:
Flashing Red
Wink command received on LonWorks
®
network
Steady OFF
Normal state
LED 4 - Network Status
This LED indicates the communication status between the module and the LonWorks® network.
LED State
Indicates:
Steady OFF
No power
Flashing Red
Receive heartbeat timeout occurred; Fieldbus communication loss indicated to host: RX_FAIL
Steady Green
Module and network are communicating correctly
Watchdog LED (WD)
This LED indicates module, drive and software status.
LED State
Indicates:
Flashing Green 1Hz Module initialized and running properly
Flashing Green 2Hz Module not initialized
Flashing Red 1Hz
Hardware check fault
Flashing Red 4Hz
Drive initialization failed
Steady Orange
Software download enabled