CAUTION:
• Do not install a unit in a rack where the internal rack ambient temperatures will exceed the
manufacturer's recommended ambient temperature for all your rack-mounted devices.
• Do not install a unit in a rack where the air flow is compromised. Ensure that air flow is not blocked
or reduced on any side, front, or back of a unit used for air flow through the unit.
• Consideration should be given to the connection of the equipment to the supply circuit so that
overloading of the circuits does not compromise the supply wiring or overcurrent protection. To
provide the correct power connection to a rack, refer to the rating labels located on the equipment
in the rack to determine the total power requirement of the supply circuit.
• (For sliding drawers) Do not pull out or install any drawer or feature if the rack stabilizer brackets
are not attached to the rack. Do not pull out more than one drawer at a time. The rack might
become unstable if you pull out more than one drawer at a time.
• (For fixed drawers) This drawer is a fixed drawer and must not be moved for servicing unless
specified by the manufacturer. Attempting to move the drawer partially or completely out of the
rack might cause the rack to become unstable or cause the drawer to fall out of the rack.
CAUTION:
Removing components from the upper positions in the rack cabinet improves rack stability during a
relocation. Follow these general guidelines whenever you relocate a populated rack cabinet within a
room or building.
• Reduce the weight of the rack cabinet by removing equipment starting at the top of the rack
cabinet. When possible, restore the rack cabinet to the configuration of the rack cabinet as you
received it. If this configuration is not known, you must observe the following precautions.
– Remove all devices in the 32U position and above.
–
Ensure that the heaviest devices are installed in the bottom of the rack cabinet.
– Ensure that there are no empty U-levels between devices installed in the rack cabinet below the
32U level.
• If the rack cabinet you are relocating is part of a suite of rack cabinets, detach the rack cabinet
from the suite.
• If the rack cabinet you are relocating was supplied with removable outriggers they must be
reinstalled before the cabinet is relocated.
• Inspect the route that you plan to take to eliminate potential hazards.
• Verify that the route that you choose can support the weight of the loaded rack cabinet. Refer to
the documentation that comes with your rack cabinet for the weight of a loaded rack cabinet.
• Verify that all door openings are at least 760 x 230 mm (30 x 80 in.).
• Ensure that all devices, shelves, drawers, doors, and cables are secure.
• Ensure that the four leveling pads are raised to their highest position.
• Ensure that there is no stabilizer bracket installed on the rack cabinet during movement.
• Do not use a ramp inclined at more than 10 degrees.
Содержание IBM Storwize V7000
Страница 1: ...Lenovo Storage V7000 Quick Installation Guide Machine Types 6538 ...
Страница 4: ...ii Lenovo Storage V7000 Quick Installation Guide ...
Страница 6: ...iv Lenovo Storage V7000 Quick Installation Guide ...
Страница 18: ......
Страница 28: ...10 Lenovo Storage V7000 Quick Installation Guide ...
Страница 54: ...36 Lenovo Storage V7000 Quick Installation Guide ...
Страница 56: ...38 Lenovo Storage V7000 Quick Installation Guide ...
Страница 63: ...Taiwan BSMI RoHS declaration Appendix C Notices 45 ...
Страница 64: ...46 Lenovo Storage V7000 Quick Installation Guide ...
Страница 67: ......
Страница 68: ......