About this task
Attention:
• Go over
“Installation Guidelines” on page 41
to ensure that you work with safety.
• Turn off the server and peripheral devices and disconnect the power cords and all external cables (see
“Power off the server” on page 13
).
• If the server is installed in a rack, slide the server out on its rack slide rails to gain access to the top cover,
or remove the server from the rack.
Watch the procedure.
A video of this procedure is available from the following link:
•
https://www.youtube.com/playlist?list=PLYV5R7hVcs-DV_Ja2E7l6T-lwN_IrnJRk
Procedure
Step 1. Unlock the security bezel with the corresponding key. It is stored at the location as illustrated.
Figure 132. Security bezel key storage location
Step 2. Remove the security bezel.
138
ThinkEdge SE450 Maintenance Manual