Lenovo makes no representations or warranties with respect to non-Lenovo
products. Support (if any) for the non-Lenovo products is provided by the third
party, not Lenovo.
Some software might differ from its retail version (if available) and might not
include user manuals or all program functionality.
Recycling information
Lenovo encourages owners of information technology (IT) equipment to
responsibly recycle their equipment when it is no longer needed. Lenovo offers a
variety of programs and services to assist equipment owners in recycling their IT
products. For information on recycling Lenovo products, go to:
http://www.lenovo.com/recycling.
Particulate contamination
Attention:
Airborne particulates (including metal flakes or particles) and reactive
gases acting alone or in combination with other environmental factors such as
humidity or temperature might pose a risk to the device that is described in this
document.
Risks that are posed by the presence of excessive particulate levels or
concentrations of harmful gases include damage that might cause the device to
malfunction or cease functioning altogether. This specification sets forth limits for
particulates and gases that are intended to avoid such damage. The limits must not
be viewed or used as definitive limits, because numerous other factors, such as
temperature or moisture content of the air, can influence the impact of particulates
or environmental corrosives and gaseous contaminant transfer. In the absence of
specific limits that are set forth in this document, you must implement practices
that maintain particulate and gas levels that are consistent with the protection of
human health and safety. If Lenovo determines that the levels of particulates or
gases in your environment have caused damage to the device, Lenovo may
condition provision of repair or replacement of devices or parts on implementation
of appropriate remedial measures to mitigate such environmental contamination.
Implementation of such remedial measures is a customer responsibility.
Table 17. Limits for particulates and gases
Contaminant
Limits
Particulate
v
The room air must be continuously filtered with 40% atmospheric dust
spot efficiency (MERV 9) according to ASHRAE Standard 52.2
1
.
v
Air that enters a data center must be filtered to 99.97% efficiency or
greater, using high-efficiency particulate air (HEPA) filters that meet
MIL-STD-282.
v
The deliquescent relative humidity of the particulate contamination
must be more than 60%
2
.
v
The room must be free of conductive contamination such as zinc
whiskers.
Gaseous
v
Copper: Class G1 as per ANSI/ISA 71.04-1985
3
v
Silver: Corrosion rate of less than 300 Å in 30 days
Appendix C. Notices
61
Содержание 5594-5KX
Страница 1: ...3U Rack or Tower UPS RT5 0kVA and RT6 0kVA Installation and User s Guide ...
Страница 2: ......
Страница 3: ...3U Rack or Tower UPS RT5 0kVA and RT6 0kVA Installation and User s Guide ...
Страница 6: ...iv Installation and User s Guide ...
Страница 18: ...xvi Installation and User s Guide ...
Страница 22: ...4 Installation and User s Guide ...
Страница 34: ...16 Installation and User s Guide ...
Страница 50: ...32 Installation and User s Guide ...
Страница 60: ...42 Installation and User s Guide ...
Страница 72: ...54 Installation and User s Guide ...
Страница 84: ...66 Installation and User s Guide ...
Страница 86: ...68 Installation and User s Guide ...
Страница 87: ......
Страница 88: ...Part Number 00WA360 Printed in USA 1P P N 00WA360 ...