Submenu
Available settings
Default settings
Battery settings
Automatic battery
test
In constant charge
mode:
[No test] [Every day]
[Every week] [Every
month]
In ABM cycling
mode:
[No test] [Every ABM
cycle]
[Every ABM cycle]
Low battery warning [0%] ... [100%]
The alarm triggers
when the set
percentage of
battery-pack capacity
is reached during
back-up time.
[20%]
Restart battery level
[0%] ... [100%]
If set, automatic
restart will occur
only when
percentage of battery
charge is reached.
[0%]
Battery charge mode
[ABM cycling]
[Constant charge]
[ABM cycling]
External battery
[Auto detection]
[Manual EBM set.]
[Manual battery set.]
[No battery]
[Auto detection]
Using standard EBM,
UPS detects
automatically the
number of EBM
connected
Deep discharge
protection
[Yes] [No]
If set to Yes, the UPS
automatically
prevents batteries
from deep discharge
by adapting end of
back-up time voltage
threshold. Warranty
void if set to No.
[Yes]
Chapter 2. Presentation
15
Содержание 5594-5KX
Страница 1: ...3U Rack or Tower UPS RT5 0kVA and RT6 0kVA Installation and User s Guide ...
Страница 2: ......
Страница 3: ...3U Rack or Tower UPS RT5 0kVA and RT6 0kVA Installation and User s Guide ...
Страница 6: ...iv Installation and User s Guide ...
Страница 18: ...xvi Installation and User s Guide ...
Страница 22: ...4 Installation and User s Guide ...
Страница 34: ...16 Installation and User s Guide ...
Страница 50: ...32 Installation and User s Guide ...
Страница 60: ...42 Installation and User s Guide ...
Страница 72: ...54 Installation and User s Guide ...
Страница 84: ...66 Installation and User s Guide ...
Страница 86: ...68 Installation and User s Guide ...
Страница 87: ......
Страница 88: ...Part Number 00WA360 Printed in USA 1P P N 00WA360 ...