DC Inverter Multi VRF System
19
(3) Calculation example.
Fig. 23
IDU:
No.
IDU
①
IDU
②
IDU
③
IDU
④
Model
Duct type
VESD024N432U
Duct type
VESD017N432U
Duct type
VESD012N432U
Duct type
VESD008N432U
Liquid pipe:
No.
A
B
C
D
Pipe size
Φ9.52
Φ9.52
Φ9.52
Φ6.35
Length
10m
5m
5m
5m
No.
a
b
c
d
Pipe size
Φ9.52
Φ6.35
Φ6.35
Φ6.35
Length
3m
3m
2m
1m
Total length of each liquid pipe
Φ9.52: A+B+C+a=10+5+5+3=23m
Φ6.35: D+b+c+d=5+3+2+1=11m
Therefore, the minimum quantity of additional refrigerant = 23×0.054+11×0.022=1.264kg
4.5 Electric Wiring
4.5.1 Notices for Wiring
(1) Install units according to national wiring codes.
(2) Use air conditioner specialized power supply and make sure that it is consistent with system’s
rated voltage.
(3) Do not pull the power cord with force.
(4) All electrical installation must be performed by qualified technicians in accordance with local
laws, regulations and this user manual.
(5) Caliber of the power cord must be large enough. A damaged power cord or connection wire
must be replaced by specialized electrical cords.
(6) If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a
similarly qualified person in order to avoid a hazard.
(7) A circuit breaker having a contact separation of at least 3mm in all poles should be fixed in fixed
wiring.
Connect the unit to specialized grounding device and make sure it is securely grounded. It’s a must
to install air switch and current circuit breaker that can cut off the power of the entire system. The circuit
Содержание VEPS075N432K
Страница 1: ...DC Inverter Multi VRF System User Manual and keep it for further reference...
Страница 2: ......
Страница 4: ......
Страница 14: ...DC Inverter Multi VRF System 8 4 2 Connection Pipe 4 2 1 Schematic Diagram of Piping Connection Fig 4...
Страница 39: ......
Страница 40: ...9 N 7 2 1 2 C 20 Lennox Industries Inc F 3 3 2 0 0 1 www lennoxglobal com...