DC Inverter Multi VRF System 

3

0

Error 

Code 

Content 

Error 

Code 

Content 

P8 

Drive IPM high temperature protection of 
compressor 

P9 

Desynchronizing protection of inverter compressor 

PH 

High-voltage protection of compressor’s 
drive DC bus bar 

PC 

Drive current detection circuit malfunction of 
compressor 

PL 

Low-voltage protection of compressor’s 
drive DC bus bar 

PE 

Phase-lacking of inverter compressor 

PF 

Drive charging circuit malfunction of 
compressor 

PJ 

Failure startup of inverter compressor 

PP 

AC current protection of inverter compressor 

H6 

Drive IPM module protection of fan 

H7 

Malfunction of drive temperature sensor of 
fan 

H8 

Drive IPM high temperature protection of fan 

H9 

Desynchronizing protection of inverter fan 

HH 

High-voltage protection of fan’s drive DC bus bar 

HC 

Drive current detection circuit malfunction of 
fan 

HL 

Low-voltage protection of fan’s drive DC bus bar 

HE 

Phase-lacking of inverter fan 

HF 

Drive charging circuit malfunction of fan 

HJ 

Failure startup of inverter fan 

HP 

AC current protection of inverter fan 

Outdoor 

Error 

Code 

Content 

Error 

Code 

Content 

E0 

Malfunction of ODU (uniform) 

E1 

High-pressure protection 

E2 

Discharge low-temperature protection 

E3 

Low-pressure protection 

E4 

High discharge temperature protection of 
compressor 

E5 

High discharge temperature protection of 
compressor 1 

F0 

Main board of ODU is poor 

F1 

Malfunction of high-pressure sensor 

F3 

Malfunction of low-pressure sensor 

F5 

Malfunction of discharge temperature sensor of 
compressor 1 

J1 

Over-current protection of compressor 1 

b1 

Malfunction of outdoor ambient temperature sensor 

b2 

Malfunction of defrosting temperature 
sensor 1 

b4 

Malfunction of liquid temperature sensor of 
sub-cooler 

b5 

Malfunction of gas temperature sensor of 
sub-cooler 

P0 

Malfunction of driving board of compressor (uniform) 

P1 

Driving board of compressor operates 
abnormally (uniform) 

P2 

Voltage protection of driving board power of 
compressor (uniform) 

P3 

Reset protection of driving module of 
compressor 

P4 

Drive PFC protection of compressor 

P5 

Over-current protection of inverter 
compressor 

H0 

Malfunction of driving board of fan (uniform) 

H1 

Driving board of fan operates abnormally 
(uniform) 

H2 

Voltage protection of driving board power of fan 
(uniform) 

H3 

Reset protection of driving module of fan 

H4 

Drive PFC protection of fan 

H5 

Over-current protection of inverter fan 

— 

 

  —

 

Debugging 

Error 

Code 

Content 

Error 

Code 

Content 

U0 

Preheat time of compressor is insufficient 

U2 

Wrong setting of ODU’s capacity code/jumper cap 

U4 

Refrigerant-lacking protection 

U5 

Wrong address for driving board of compressor 

U6 

Alarm because valve is abnormal 

U8 

Short-circuit malfunction of IDU 

U9 

Malfunction of pipe-line for ODU 

UC 

Setting of main IDU is successful 

UL 

Wrong button-dial 

UE 

Charging of refrigerant is invalid 

C0 

Communication malfunction between IDU, 
ODU and IDU’s wired controller 

C2 

Communication malfunction between main control 
and inverter compressor driver 

Содержание VEPS075N432K

Страница 1: ...DC Inverter Multi VRF System User Manual and keep it for further reference...

Страница 2: ......

Страница 3: ...ore reusing it 3 Please properly select the model according to actual using environment otherwise it may impact the using convenience 4 This product has gone through strict inspection and operational...

Страница 4: ......

Страница 5: ...turer 3 After verification the defect of product is directly caused by corrosive gas 4 After verification defects are due to improper operation during transportation of product 5 Operate repair mainta...

Страница 6: ...it and Mounting Hole 7 4 2 Connection Pipe 8 4 3 Installation of Connection Pipe 12 4 4 Vacuum Pumping Refrigerant Adding 17 4 5 Electric Wiring 19 5 Check Items after Installation and Test Operation...

Страница 7: ...Follow this manual to complete the installation work Please read this manual carefully before turning on or repairing the unit Installation should be performed by the distributor or qualified technic...

Страница 8: ...gen deficit when gas heater or oil heater is used in the room Never plug in or unplug the power plug directly to turn on or turn off the air conditioner Once the air conditioner is turned on it can be...

Страница 9: ...tion concerning use of the appliance in a safe way and understand the hazards involved Children shall not play with the appliance Cleaning and user maintenance shall not be made by children without su...

Страница 10: ...l capacity of indoor units should be within 50 135 of that of the outdoor unit Model Max sets of connectable IDUs VEPS075N432K 13 VEPS096N432K 17 VEPS120N432K 20 3 can be connected to various indoor u...

Страница 11: ...injury or even death Item needs to be followed Improper operation might lead to personal injury or property damage Select a location which is strong enough to hold unit s weight so that unit can stand...

Страница 12: ...quirements Refer to the table below for piping work requirements R410A Refrigerant System Outer diameter mm inch Wall thickness mm 6 35 1 4 0 8 9 52 3 8 0 8 12 7 1 2 0 8 15 9 5 8 1 0 19 05 3 4 1 0 22...

Страница 13: ...m 7 4 1 Dimension of Outdoor Unit and Mounting Hole Unit Outline and Installation Dimension mm Fig 3 Unit mm Model A B C D E VEPS075N432K 940 320 1430 632 350 VEPS096N432K 940 460 1615 610 486 VEPS120...

Страница 14: ...DC Inverter Multi VRF System 8 4 2 Connection Pipe 4 2 1 Schematic Diagram of Piping Connection Fig 4...

Страница 15: ...wable Length and Height Difference of Connection Pipe Piping parameters of VEPS075N432K VEPS096N432K VEPS120N432K Allowable value Fitting pipe Total length actual length of fitting pipe 300m L1 L2 L3...

Страница 16: ...f pipe from ODU to the 1st indoor branch will be determined by the dimension of outdoor connection pipe Fig 6 Dimension of outdoor connection pipe Basic module Pipe dimension Connection method Gas pip...

Страница 17: ...oor units X kW Model Y type branch X 20 VEBC01A 20 X 30 VEBC01B 30 X 70 VEBC02A 70 X 135 VEBC03A 135 X VEBC04A 4 2 5 Dimension of Pipe between Indoor Branches Select pipe between indoor branches accor...

Страница 18: ...tween indoor and outdoor units Keep the number of bends as little as possible Radius of curvature should be as large as possible 2 Weld the connection pipe between indoor and outdoor units Please stri...

Страница 19: ...oint Twist on the flared nut tightly by hand as in Fig 13 Make sure indoor pipe is correctly connected Improper location of the center will prevent flared nut from being securely twisted Thread of nut...

Страница 20: ...ng gun to unsolder straight pipe 1 and straight pipe 2 Install connection pipe 1 and connection pipe 2 to the corresponding position and then seal the apertures with welding rod First weld the liquid...

Страница 21: ...plate rear side plate and connection board Then open the soundproof cotton Use a soldering gun to unsolder connection pipe 1 and connection pipe 2 Rotate them to a proper angle and install them to the...

Страница 22: ...match with various copper pipes Use pipe cutter to cut in the middle of the pipe section that is of proper dimension and remove burrs as well See Fig 20 3 Y type branch must be installed vertically o...

Страница 23: ...een pipe and wall See Fig 21 Fig 21 5 Thermal insulating material of branches should be the same as that of the pipeline The attached foam of branches cannot be taken as insulating material 6 When wra...

Страница 24: ...s service 2 Calculation of the amount of additional refrigerant Calculation method of the quantity of additional refrigerant based on liquid pipe Quantity of additional refrigerant length of liquid pi...

Страница 25: ...re that it is consistent with system s rated voltage 3 Do not pull the power cord with force 4 All electrical installation must be performed by qualified technicians in accordance with local laws regu...

Страница 26: ...nding terminal Do not connect the ground wire to the following Water pipe Gas pipe Drain pipe Other places that are deemed as not secured by professional technicians 4 5 2 Wiring Diagram 1 Connection...

Страница 27: ...er is 40 C If working condition changes please adjust the specification according to national standard 4 5 3 Engineering Wiring of Power Supply and Communication Cable 1 Please refer Fig 26 and 27 for...

Страница 28: ...op shake or emit noise Gas leakage test is taken or not Insufficient cooling heating capacity Unit gets proper thermal insulation or not There may be condensation and dripping Drainage is smooth or no...

Страница 29: ...hread ends and forceps holder must be removed from the unit 5 Check whether unit s appearance and pipeline system has been damaged during transportation 6 Calculate the quantity of refrigerant that ne...

Страница 30: ...main board s SW3 button for 5s to start debugging 01 ON 2s later next step starts 02_ Allocate addresses 02 Ad Display circularly System is allocating addresses 10s later display as below 02 L7 Displ...

Страница 31: ...he ratio is out of range unit will display as below 05 CH Display circularly Rated capacity ratio of IDU is too high Change the combination way of IDU and ODU to make the ratio within range And restar...

Страница 32: ...Press main board s SW4 button and display shows 09 OC Then check if the gas and liquid valves of ODU are completely open After confirmation press the SW4 button again Then compressor will start runni...

Страница 33: ...value will be within 44 53 C In heating mode if ambient temp is above 5 C system s high pressure value is within 40 52 C If ambient temp is low and many IDUs are turned on the high pressure will be lo...

Страница 34: ...Please check the items below before calling for maintenance Problems Causes What to do Unit doesn t work Fuse or circuit breaker is cut off Replace fuse or reset the circuit breaker Power failure Res...

Страница 35: ...over current protection Indoor Error Code Content Error Code Content L0 Malfunction of IDU uniform L1 Protection of indoor fan L2 Auxiliary heating protection L3 Water full protection L4 Over current...

Страница 36: ...high pressure sensor F3 Malfunction of low pressure sensor F5 Malfunction of discharge temperature sensor of compressor 1 J1 Over current protection of compressor 1 b1 Malfunction of outdoor ambient...

Страница 37: ...ging refrigerant automatically AE Charging refrigerant manually AF Fan AJ Alarm for cleaning filter AP Debugging confirmation for startup of unit AU Long distance emergency stop Ab Emergency stop of o...

Страница 38: ...nits 4 If outdoor unit has rust please apply some paint to it so as to prevent the rust from growing 8 5 Parts Replacement Parts and components can be obtained from nearby LENNOX office or LENNOX dist...

Страница 39: ......

Страница 40: ...9 N 7 2 1 2 C 20 Lennox Industries Inc F 3 3 2 0 0 1 www lennoxglobal com...

Отзывы: