background image

Page 13

Oil Supply Line & Filter Connections

One−Pipe Systems

CAUTION

Do not install the bypass plug into the pump on one−
pipe systems.

The burner is shipped with a single−stage fuel pump set for
one−pipe operation. For one−pipe systems, the oil supply
pipe is connected to the inlet tap on the pump. A one−pipe
system should only be used where there is gravity oil flow to
the pump or there is no more than 8 ft. of vertical lift (or 6 in.
Hg) from the oil tank to the fuel pump.
 1 − Connect the inlet pipe to the pump inlet. Start the burner.
 2 − Turn the bleed valve one turn counterclockwise.
 3 − Bleed the unit until all air bubbles disappear.

NOTE − Hurried bleeding will prevent the unit from op-
erating properly.

 4 − If  necessary,  put  GeniSys

t

 primary control into its

4−minute pump priming mode. Refer to table 10.

 5 − Tighten the bleed valve securely.

Two−Pipe Systems

 

(Figure 13)

If the installation requires a two−pipe operation, install the
bypass plug included in the bag which is attached to the
pump. To convert the pump, install the bypass plug accord-
ing to the provided pump instructions. Notice in the two-pipe
system the return pipe must terminate in the tank 3" (76 mm)
to 4" (102 mm) above the supply inlet. Ensure the return pipe
terminates at the correct measurement or air may escape
into the system. This could result in loss of prime.

NOTE− If using an outside tank in cold climates a number
one fuel or an oil treatment is strongly recommended. Con-
tact your oil supplier for oil treatment, if necessary.

 1 − Remove 1/4" plug from return port.
 2 − Insert bypass plug and tighten it.
 3 − Attach the return and inlet pipes. Start the burner. Air

bleeding is automatic.

NOTE − If a faster bleed is necessary, open the bleed
valve.

 4 − The return pipe must terminate 3" to 4" above the sup-

ply pipe inlet.

NOTE − If the return pipe does not terminate where it
should, air may enter the system, and prime may be
lost.

An oil filter is required for all models. 

Install filter inside

the building between the tank shut-off valve and the burner.
Locate filter close to (but at least 3 feet away from) the burn-
er for easy maintenance. Table 6 lists the filters for the
SLO183B furnace.

Consult the burner manufacturer’s instructions that are in-
cluded with the unit for further details concerning oil supply
pipe connections.

Table 6

Oil Filters (All Models)

Oil Filters

Cat. 

Number

10 micron filter (no mounting bracket)

81P89

10 micron filter (mounting bracket)

53P92

10 micron replacement cartridge for filter, 45 gph

53P93

Filter restriction indicator gauge

53P90

Leak Check

After oil piping is completed, carefully check all piping con-
nections (factory and field) for oil leaks.

Oil Line Heater (Optional)

A heater for the oil pipe is available for applications that are
located in cold climates. The heater warms the oil pipe to
assist the initial start−up. An oil line heater is available from
Beckett using part number 51621 (Beckett Start Helper).

Electrical Wiring

All wiring must conform to the National Electric Code
(NEC), or Canadian Electric Code (CEC) and any local
codes. Refer to figure 14 for typical unit wiring diagram.
See figures  and  for field wiring. Refer to figure 18 for termi-
nal designations on blower control.
 1 − Refer to appliance rating plate for proper fuse size.
 2 − Install room thermostat and make wire connections to

the fan control board. Avoid installing thermostat on an
outside wall or where it can be affected by radiant heat.
Set the adjustable heat anticipator on thermostat ac-
cording to the wiring diagram sticker provided on unit.

 3 − Install a separate fused disconnect switch near unit so

power can be shut off for servicing.

 4 − Complete  line  voltage  wiring  from  disconnect switch

near unit to make-up box.

NOTE − An equipment ground screw is provided. Refer
to unit wiring diagram. Ground unit using a suitable
ground wire.

 5 − Any 120V accessory rated up to 1 amp can be con-

nected to the EAC terminal on the A15 ST9103A con-
trol. The EAC terminal is energized when the blower is
in operation.

 6 − A  24V  dehumidistat  or  ComfortSense

®

 7000 input

(from terminal D) can be connected to the reverse−act-
ing HUM terminal on the A54 blower control. See figure
18.

Содержание SLO183BF101/114V42

Страница 1: ...O183BV Start Up Performance Check List 2 SLO183BV Unit Parts Arrangement 3 SLO183BV AFG Burner Parts Arrangement 3 Requirements 4 Combustion and Ventilation Air 5 Locate Level Unit 6 Nozzle Adjustment...

Страница 2: ...1334 27 686 18 x 21 457 x 533 18 x 16 457 x 406 SLO183BF135 150V60 22 1 2 572 37 940 52 1 2 1334 27 686 21 x 21 533 x 533 21 x 16 533 x 406 SLO183BR135 150V60 22 1 2 572 37 940 52 1 2 1334 27 686 21 x...

Страница 3: ...eat Exchanger Blower Control A54 Not Visible Located on blower housing Clean Out Port SLO183BV AFG Burner Parts Arrangement ESCUTCHEON PLATE MAIN HOUSING HEAT SHIELD BURNER CONTROL with Reset Button O...

Страница 4: ...is strongly recommended especially in new homes Refer to table 1 or the unit plate for specific combus tion air opening dimensions Table 1 Combustion Air Opening Dimensions Model No Combustion Air Ope...

Страница 5: ...a basement or large equipment room with a volume greater than 50 cubic feet 1 4 cubic meters per 1 000 Btu 293 W per hour of the combined input rating of all appliances installed in that space This s...

Страница 6: ...rs will have 20 to 25 per cent free area and metal louvers and grilles will have 60 to 75 percent free area Louvers and grilles must be fixed in the open position or interlocked with the equipment so...

Страница 7: ...114 and 150 units Inspect the spark transformer leads also to en sure they are still attached to the electrodes The burner assembly is attached to the vestibule panel by three nuts Slots are provided...

Страница 8: ...rd ing to the requirements of the National Fire Protection Asso ciation The smallest dimensions of the chimney should be at least equal to the diameter of the furnace vent connector Make sure the chim...

Страница 9: ...not be less than the area of the largest vent or vent connection plus 50 of the area of the additional vent or vent con nection Chimney must be able to sufficiently vent all appliances operating at th...

Страница 10: ...hting instruction on the unit place the appliance being inspected in operation Adjust ther mostat so appliance will operate continuously 5 Test for spillage using a draft gauge 6 After it has been det...

Страница 11: ...edures that should be followed when installing the supply air plenum 1 Use sealing strips of fiberglass 2 In all cases the plenum should be secured to furnace or evaporator cabinet with sheet metal sc...

Страница 12: ...ings IMPORTANT Both oil supply and return pipes must be submerged in oil in the supply tank Table 4 Two Pipe Maximum Pipe Length H R Lift H 3450 RPM 3 GPH 11 4 LPH 3 8 10 mm OD Tubing 1 2 12 mm OD Tub...

Страница 13: ...een the tank shut off valve and the burner Locate filter close to but at least 3 feet away from the burn er for easy maintenance Table 6 lists the filters for the SLO183B furnace Consult the burner ma...

Страница 14: ...hrough specified high voltage opening Do not com bine voltage in one opening CAUTION Use copper conductors only IMPORTANT If using a programmable thermostat be sure to use a type of thermostat that re...

Страница 15: ...ams 1 Heat 1 Cool ComfortSense 7000 L7724U 1 Heat 2 Cool ComfortSense 7000 L7724U 1 Heat 1 Cool ComfortSense 7000 L7724U with Thermostat Dehumidification Mode 1 Heat 2 Cool ComfortSense 7000 L7724U wi...

Страница 16: ...age Heat Pump ComfortSense 7000 L7724U with Dual Fuel Control Mode Dual Fuel Two Stage Heat Pump ComfortSense 7000 L7724U with Dual Fuel Control Mode Dual Fuel Two Stage Heat Pump ComfortSense 7000 L7...

Страница 17: ...de mand is satisfied OFF CALL 100 82 Y 60 sec 7 5 minutes 82 y Y Cool Demand Present y Cool Demand Satisfied When the demand for cool is met the blower ramps down to 82 CFM for 60 seconds then turns...

Страница 18: ...times the light may appear to flicker or glow This takes place when the control is communicating with the motor be tween cycles This is normal operation After the CFM for each application has been de...

Страница 19: ...1600 755 1200 565 N A N A Same as NORM N A N A Same as NORM 1700 800 1530 720 1360 640 1020 480 NOTE Continuous Fan air volume is 50 of COOL speed Blower Control A54 Figure 18 16 PIN PLUG BOARD TO MOT...

Страница 20: ...n tempera tures in the supply and return air plenums should approxi mate the temperatures listed in table 8 and on the ap pliance rating plate If the temperature rise is not within the range listed ch...

Страница 21: ...hings which might affect combustion Those things which might affect combustion can then do so without causing the unit to start sooting smoking Things which might affect combustion include a nozzle go...

Страница 22: ...rossover tube CAUTION Do not attempt to clean the combustion chamber It can be easily damaged 5 Replace the clean out caps and flue access elbow Make sure locking screws are secure 6 Brush out and vac...

Страница 23: ...f as long as the button is held Enables pump priming After the reset button has been held for 15 seconds The button can then be clicked during the next ignition sequence to enter pump prime mode Run i...

Страница 24: ...oft lockout reset oil primary control allows second ignition attempt Primary control enters hard lockout after second ignition failure 15 sec onds without flame being sensed Push reset but ton on prim...

Страница 25: ...speed ramps down Circulat ing fan shuts off after 60 seconds Thermostat begins call for fan G terminal is energized Indoor blower is energized immediately at 50 of cool speed ST9103A may be factory co...

Страница 26: ...ect the flame detector wires at the primary control If the burner starts fault is in the detector circuit Flame detector leads are shorted Separate leads Flame detector exposed to light Seal off false...

Страница 27: ...from unit Inspect the nozzle for plugged orifice or carbon build up around orifice Nozzle orifice plugged Replace nozzle with the same size spray angle and spray pattern Nozzle strainer plugged Poor o...

Страница 28: ...ter burner fires immedi ately jumper across flame detector termi nals at the pri mary control If burner con tinues to run does not lock out of safety fault may be due to poor fire Inspect fire Unbalan...

Страница 29: ...wheel dirty Clean blower wheel Wrong motor rotation Replace motor Restrictions in return or supply air system Correct cause of restriction Power If voltage fluctuates fault is in the power source Rech...

Страница 30: ...ed heat exchanger Clean heat exchanger Readjust burner Insufficient overfire draft Increase draft Incorrect nozzle assembly depth Set to 1 13 Too little combustion air Increase combustion air High sta...

Отзывы: