background image

Page 28

505328M 06/09

PROGRAMMABLE THERMOSTATS

Your Lennox system may be controlled by a
programmable thermostat. These thermostats provide the
added feature of programmable time-of-day setpoints for
both heating and cooling. Refer to the user’s information
manual provided with your particular thermostat for
operation details.

PRESERVICE CHECK

If your system fails to operate, check the following before
calling for service:

S

Check to see that all electrical disconnect switches are
ON.

S

Make sure the room thermostat temperature selector
and system switch (HEAT, COOL and AUTO) are
properly set.

S

Check for any blown fuses or tripped circuit breakers.

S

Make sure unit access panels are in place.

S

Make sure air filter is clean.

S

If service is needed, locate and write down the unit
model number and have it handy before calling.

OPTIONAL ACCESSORIES

Optional accessories for the XP15 include the following
(also, see Engineering Handbook for more details):

S

Compressor starter kit

S

Low ambient kit

S

Vapor line drier

S

Wire tie kit

S

Snow Guard (X8782)

S

Snow Shield Kit (44W14)

Start−Up and Performance Checklist

Customer 

Address

Indoor Unit Model

Serial

Outdoor Unit Model

Serial

Notes:

START−UP CHECKS

Refrigerant Type:
Rated Load Amps

Actual Amps

Rated Volts

Actual Volts

Condenser Fan Full Load Amps

Actual Amps:

COOLING MODE

Vapor Pressure: 

Liquid Pressure:

Supply Air Temperature:

Ambient Temperature:

Return Air Temperature:

HEATING MODE

Vapor Pressure: 

Liquid Pressure:

Supply Air Temperature:

Ambient Temperature:

Return Air Temperature:

System Refrigerant Charge (Refer to manufacturer’s information on unit or installation instructions for required subcooling and approach
temperatures.)

Subcooling:

A

B

=

SUBCOOLING

Saturated Condensing Temperature (A)

minus

 Liquid Line Temperature (B)

Approach:

A

B

=

APPROACH

Liquid Line Temperature (A)

minus 

Outdoor Air Temperature (B)

Indoor Coil Temp. Drop (18 to 22°F)

A

B

=

COIL TEMP DROP

Return Air Temperature (A)

minus

 Supply Air Temperature (B)

Содержание Signature XP15-024

Страница 1: ...ping and Packing List 1 Unit Dimensions 2 General Information 2 Recovering Refrigerant from Existing System 4 Positioning New Outdoor Unit 5 Removing Panel 6 Electrical Connections 7 New or Replacemen...

Страница 2: ...will expose you to fiberglass wool dust Breathing this may cause lung cancer Fiberglass wool is known to the State of California to cause cancer Fiberglass wool may also cause respiratory skin and eye...

Страница 3: ...rvice Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap using an appropriately sized wrench 2 Connect gauge to the...

Страница 4: ...e 90 To close rotate Stem clockwise 90 Service Port Service Port Cap STEM CAP Valve Stem Open to line set when valve is closed to both line set and unit when valve is open Figure 3 Ball Type Service V...

Страница 5: ...r as possible from the property line When possible do not install the unit directly outside a window Glass has a very high level of sound transmission For proper placement of unit in relation to a win...

Страница 6: ...side louvered panels to expose the unit base pan Install the brackets as illustrated in figure 10 using conventional practices replace the panels after installation is complete IMPORTANT Using field p...

Страница 7: ...panel firmly throughout this procedure Rotate bottom corner of panel away from hinged corner post until lower three tabs clear the slots as illustrated in figure 12 detail B 3 Move panel down until li...

Страница 8: ...pply to unit from a properly sized disconnect switch as illustrated in figure 15 4 Ground unit from ground lug as illustrated in figure 15 to unit disconnect switch or to an earth ground Figure 14 Typ...

Страница 9: ...te the following points S Model XP15 and size e g 060 of unit S Line set diameters for the unit being installed from table 3 S Number of elbows and if there is a rise or drop of the piping Line sets f...

Страница 10: ...ruction Shown STRAP LIQUID LINE TO VAPOR LINE METAL SLEEVE AUTOMOTIVE MUFFLER TYPE HANGER WALL STUD VAPOR LINE WRAPPED IN ARMAFLEX LIQUID LINE ANCHORED HEAVY NYLON WIRE TIE STRAP LIQUID LINE TO VAPOR...

Страница 11: ...o protect the base paint Also shield the light maroon R 410A sticker 5 Flow regulated nitrogen at 1 to 2 psig through the refrigeration gauge set into the valve stem port connection on the liquid line...

Страница 12: ...gerant added to the system earlier is measurable with a leak detector 11 After leak testing disconnect gauges from service ports Removing Service Valve Port Core Remove both of the outdoor unit s serv...

Страница 13: ...system NOTE A single system flush should remove all of the mineral oil from the existing refrigerant lines and indoor unit coil A second flushing may be done using clean refrigerant if insufficient am...

Страница 14: ...nit s service port cores liquid and vapor as illustrated in figure 24 DO NOT INSTALL CAPS AT THIS TIME INSTALL SERVICE PORT CORES OUTDOOR UNIT LIQUID AND VAPOR SERVICE VALVES Figure 24 Typical Service...

Страница 15: ...er evacuation is complete open the liquid line and vapor line service valves to release the refrigerant charge contained in outdoor unit into the system 4 Replace the stem caps and tighten as specifie...

Страница 16: ...4 Adjust the fan speed See indoor unit instructions to in crease decrease fan speed Changing air flow affects all temperatures recheck tempera tures to confirm that the temperature drop and DT are wit...

Страница 17: ...record it in the SAT space 8 Subtract LIQ temp from SAT temp to determine subcooling record it in SC space 9 Compare SC results with table below being sure to note any additional charge for line set...

Страница 18: ...48C 7 5 0 7 CH33 49C 5 5 0 12 CH33 62D 5 7 0 14 CR33 48C 37 4 0 5 CR33 50 60 32 5 0 10 CX34 31 15 4 0 0 CX34 38 SN 6007 and after 4 4 0 3 CX34 38 before SN 6007 13 4 0 3 CX34 43 7 5 0 7 CX34 44 48 13...

Страница 19: ...GHT An emergency heat function is designed into some room thermostats This feature is applicable when isolation of the outdoor unit is required or when auxiliary electric heat is staged by outdoor the...

Страница 20: ...running only briefly 1 Thermostat demand signal is intermittent 2 Time delay relay or DCB is defective 3 If high pressure switch is present see Flash Code 2 information 4 If low pressure switch is pre...

Страница 21: ...Check or Service LED or it may come on solid Confirm fault by observing and interpreting the code from the LSOM yellow alert LED at the unit Defrost System DEFROST CONTROL BOARD DCB FUNCTION The DCB...

Страница 22: ...nal sounds that may occur while the unit is cycling in and out of the defrost mode When a jumper is installed on the DELAY pins the compressor will be cycled off for 30 seconds going in and out of the...

Страница 23: ...istance values can be checked by ohming across pins shown in table 15 NOTE When checking the ohms across a sensor be aware that a sensor showing a resistance value that is not within the range shown i...

Страница 24: ...e installed or incorrect operation of metering de vice 4 Incorrect or improper sensor location or connection to system 1 Remove any blockages or restrictions from coils and or fans Check indoor and ou...

Страница 25: ...the Demand Defrost Control Y1 Active Place a jumper on TEST pins for longer than one second but less than two seconds Clears any short cycle lockout and five strike fault lockout function if applicabl...

Страница 26: ...the start of each heating and cooling season the following service checks should be performed by a qualified service technician First turn off electrical power to the unit prior to performing unit mai...

Страница 27: ...ing cycle when temperatures are below 45 F 7 C An electronic control activates a defrost cycle lasting 5 to 15 minutes at preset intervals to clear the outdoor coil of the frost S During the defrost c...

Страница 28: ...5 include the following also see Engineering Handbook for more details S Compressor starter kit S Low ambient kit S Vapor line drier S Wire tie kit S Snow Guard X8782 S Snow Shield Kit 44W14 Start Up...

Отзывы: