background image

Page 24

505328M 06/09

TEST

See Figure 33 for details concerning Test Mode
operations.

NORMAL

The DCB monitors the O line, to determine the system
operating mode (heat/cool), outdoor ambient temperature,
coil temperature (outdoor coil) and compressor run time to
determine when a defrost cycle is required.

CALIBRATION

The DCB is considered uncalibrated when power is
applied to the DCB, after cool mode operation, or if the coil
temperature exceeds the termination temperature when it
is in heat mode.

DEFROST

For detail information on DEFROST MODE, see 

Detail

Defrost Mode Operation

 on page 26.

Table 16. DCB Diagnostic LEDs

DS2
Green

DS1
Red

Condition

Possible Cause(s)

Solution

OFF

OFF

Power problem

No power (24V) to DCB terminals R and
C or DCB failure.

1

Check control transformer power (24V).

2

If power is available to DCB and LED(s) do not light,
replace DCB.

SIMULTANEOUS
SLOW FLASH

Normal operation

Unit operating normally or in standby
mode.

None required.

ALTERNATING
SLOW FLASH

5−minute anti−short cycle delay

Initial power up, safety trip, end of room
thermostat demand.

None required (Jumper TEST pins to override)

SIMULTANEOUS
FAST FLASH

Ambient sensor problem

Sensor being detected open or shorted or out of temperature range. DCB will revert to
time/temperature defrost operation. (System will still heat or cool).

ALTERNATING
FAST FLASH

Coil sensor problem

Sensor being detected open or shorted or out of temperature range. DCB will not perform demand
or time/temperature defrost operation. (System will still heat or cool).

ON

ON

DCB failure

Indicates that DCB has internal component failure. Cycle 24 volt power to DCB. If code does not
clear, replace DCB.

FAULT and LOCKOUT CODES 

(

Each fault adds 1 strike to that code’s counter; 5 strikes per code = LOCKOUT

)

OFF

SLOW
FLASH

Low pressure fault

1

Restricted air flow over indoor or out-
door coil.

2

Improper refrigerant charge in sys-
tem.

3

Improper metering device installed or
incorrect operation of metering de-
vice.

4

Incorrect or improper sensor location
or connection to system.

1

Remove any blockages or restrictions from coils
and/or fans. Check indoor and outdoor fan motor for
proper current draws.

2

Check system charge using approach and
subcooling temperatures.

3

Check system operating pressures and compare to
unit charging charts.

4

Make sure all pressure switches and sensors have
secure connections to system to prevent refrigerant
leaks or errors in pressure and temperature
measurements.

OFF

ON

Low pressure lockout

SLOW
FLASH

OFF

High pressure fault

ON

OFF

High pressure lockout

Units WITH Discharge Line Sensor

SLOW
FLASH

ON

Discharge line temperature
fault

This code detects shorted sensor or high discharge temperatures. If the discharge line temperature
exceeds a temperature of 300ºF (148ºC) during compressor operation, the board will de−energize
the compressor contactor output (and the defrost output if active). The compressor will remain off
until the discharge temperature has dropped below 225ºF (107ºC).

FAST
FLASH

ON

Discharge line temperature
Lockout

OFF

FAST
FLASH

Discharge sensor fault

The board detects open sensor or out of temperature sensor range. This fault is detected by allow-
ing the unit to run for 90 seconds before checking sensor resistance. If the sensor resistance is not
within range after 90 seconds, the board will count one fault. After five faults, the board will lockout.

FAST
FLASH

OFF

Discharge sensor lockout

Units WITHOUT Discharge Line Sensor

SLOW
FLASH

ON

Discharge line temperature
fault

Some heat pump units do not use a defrost line sensor. Therefore this code is not applicable.

FAST
FLASH

ON

Discharge line temperature
lockout

OFF

FAST
FLASH

Discharge sensor fault

Some heat pump units do not use a defrost line sensor. However, on these units a resistor is
installed across pins P4−1 and P4−2. If the resistor is missing or damaged then this fault code will
be displayed.

FAST
FLASH

OFF

Discharge sensor lockout

Some heat pump units do not use a defrost line sensor. Therefore this code is not applicable.

Содержание Signature XP15-024

Страница 1: ...ping and Packing List 1 Unit Dimensions 2 General Information 2 Recovering Refrigerant from Existing System 4 Positioning New Outdoor Unit 5 Removing Panel 6 Electrical Connections 7 New or Replacemen...

Страница 2: ...will expose you to fiberglass wool dust Breathing this may cause lung cancer Fiberglass wool is known to the State of California to cause cancer Fiberglass wool may also cause respiratory skin and eye...

Страница 3: ...rvice Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap using an appropriately sized wrench 2 Connect gauge to the...

Страница 4: ...e 90 To close rotate Stem clockwise 90 Service Port Service Port Cap STEM CAP Valve Stem Open to line set when valve is closed to both line set and unit when valve is open Figure 3 Ball Type Service V...

Страница 5: ...r as possible from the property line When possible do not install the unit directly outside a window Glass has a very high level of sound transmission For proper placement of unit in relation to a win...

Страница 6: ...side louvered panels to expose the unit base pan Install the brackets as illustrated in figure 10 using conventional practices replace the panels after installation is complete IMPORTANT Using field p...

Страница 7: ...panel firmly throughout this procedure Rotate bottom corner of panel away from hinged corner post until lower three tabs clear the slots as illustrated in figure 12 detail B 3 Move panel down until li...

Страница 8: ...pply to unit from a properly sized disconnect switch as illustrated in figure 15 4 Ground unit from ground lug as illustrated in figure 15 to unit disconnect switch or to an earth ground Figure 14 Typ...

Страница 9: ...te the following points S Model XP15 and size e g 060 of unit S Line set diameters for the unit being installed from table 3 S Number of elbows and if there is a rise or drop of the piping Line sets f...

Страница 10: ...ruction Shown STRAP LIQUID LINE TO VAPOR LINE METAL SLEEVE AUTOMOTIVE MUFFLER TYPE HANGER WALL STUD VAPOR LINE WRAPPED IN ARMAFLEX LIQUID LINE ANCHORED HEAVY NYLON WIRE TIE STRAP LIQUID LINE TO VAPOR...

Страница 11: ...o protect the base paint Also shield the light maroon R 410A sticker 5 Flow regulated nitrogen at 1 to 2 psig through the refrigeration gauge set into the valve stem port connection on the liquid line...

Страница 12: ...gerant added to the system earlier is measurable with a leak detector 11 After leak testing disconnect gauges from service ports Removing Service Valve Port Core Remove both of the outdoor unit s serv...

Страница 13: ...system NOTE A single system flush should remove all of the mineral oil from the existing refrigerant lines and indoor unit coil A second flushing may be done using clean refrigerant if insufficient am...

Страница 14: ...nit s service port cores liquid and vapor as illustrated in figure 24 DO NOT INSTALL CAPS AT THIS TIME INSTALL SERVICE PORT CORES OUTDOOR UNIT LIQUID AND VAPOR SERVICE VALVES Figure 24 Typical Service...

Страница 15: ...er evacuation is complete open the liquid line and vapor line service valves to release the refrigerant charge contained in outdoor unit into the system 4 Replace the stem caps and tighten as specifie...

Страница 16: ...4 Adjust the fan speed See indoor unit instructions to in crease decrease fan speed Changing air flow affects all temperatures recheck tempera tures to confirm that the temperature drop and DT are wit...

Страница 17: ...record it in the SAT space 8 Subtract LIQ temp from SAT temp to determine subcooling record it in SC space 9 Compare SC results with table below being sure to note any additional charge for line set...

Страница 18: ...48C 7 5 0 7 CH33 49C 5 5 0 12 CH33 62D 5 7 0 14 CR33 48C 37 4 0 5 CR33 50 60 32 5 0 10 CX34 31 15 4 0 0 CX34 38 SN 6007 and after 4 4 0 3 CX34 38 before SN 6007 13 4 0 3 CX34 43 7 5 0 7 CX34 44 48 13...

Страница 19: ...GHT An emergency heat function is designed into some room thermostats This feature is applicable when isolation of the outdoor unit is required or when auxiliary electric heat is staged by outdoor the...

Страница 20: ...running only briefly 1 Thermostat demand signal is intermittent 2 Time delay relay or DCB is defective 3 If high pressure switch is present see Flash Code 2 information 4 If low pressure switch is pre...

Страница 21: ...Check or Service LED or it may come on solid Confirm fault by observing and interpreting the code from the LSOM yellow alert LED at the unit Defrost System DEFROST CONTROL BOARD DCB FUNCTION The DCB...

Страница 22: ...nal sounds that may occur while the unit is cycling in and out of the defrost mode When a jumper is installed on the DELAY pins the compressor will be cycled off for 30 seconds going in and out of the...

Страница 23: ...istance values can be checked by ohming across pins shown in table 15 NOTE When checking the ohms across a sensor be aware that a sensor showing a resistance value that is not within the range shown i...

Страница 24: ...e installed or incorrect operation of metering de vice 4 Incorrect or improper sensor location or connection to system 1 Remove any blockages or restrictions from coils and or fans Check indoor and ou...

Страница 25: ...the Demand Defrost Control Y1 Active Place a jumper on TEST pins for longer than one second but less than two seconds Clears any short cycle lockout and five strike fault lockout function if applicabl...

Страница 26: ...the start of each heating and cooling season the following service checks should be performed by a qualified service technician First turn off electrical power to the unit prior to performing unit mai...

Страница 27: ...ing cycle when temperatures are below 45 F 7 C An electronic control activates a defrost cycle lasting 5 to 15 minutes at preset intervals to clear the outdoor coil of the frost S During the defrost c...

Страница 28: ...5 include the following also see Engineering Handbook for more details S Compressor starter kit S Low ambient kit S Vapor line drier S Wire tie kit S Snow Guard X8782 S Snow Shield Kit 44W14 Start Up...

Отзывы: