background image

Page 26

505328M 06/09

DETAILED DEFROST MODE OPERATION

The defrost mode has three basic operational modes
which are defrost cycles, actuation and termination. These
modes are described as follows:

Defrost Cycles

The demand DCB initiates a defrost

cycle based on either 

frost detection 

or 

time

.

Event

Description

Frost
Detection

If the compressor runs longer than 30
minutes and the actual difference between
the clear coil and frosted coil temperatures
exceeds the maximum difference allowed
by the DCB, a defrost cycle will be initiated.

IMPORTANT − The DCB will allow a
greater accumulation of frost and will
initiate fewer defrost cycles than a
time/temperature defrost system.

Time

If six hours of heating mode compressor
run time has elapsed since the last defrost
cycle while the coil temperature remains
below 35°F (2°C), the DCB will initiate a
defrost cycle.

Actuation

When the reversing valve is de−energized,

the Y1 circuit is energized, and the coil temperature is
below 35°F (2°C), the DCB logs the compressor run time.
If the DCB is not calibrated, a defrost cycle will be initiated
after 30 minutes of heating mode compressor run time.
The DCB will attempt to self−calibrate after this (and all
other) defrost cycle(s).

Calibration success depends on stable system
temperatures during the 20−minute calibration period. If
the DCB fails to calibrate, another defrost cycle will be
initiated after 45 minutes of heating mode compressor run
time. Once the DCB is calibrated, it initiates a demand
defrost cycle when the difference between the clear coil
and frosted coil temperatures exceeds the maximum
difference allowed by the DCB or after six hours of heating
mode compressor run time has been logged since the last
defrost cycle.

NOTE − If ambient or coil fault is detected, the DCB will not
execute the TEST mode.

Termination

The defrost cycle ends when the coil

temperature exceeds the termination temperature or after
14 minutes of defrost operation. If the defrost is terminated
by the 14−minute timer, another defrost cycle will be
initiated after 30 minutes of run time.

DCB DIAGNOSTICS

See table 16 on page 24 to determine DCB operational
conditions and to diagnose cause and solution to
problems.

Maintenance

Before the start of each heating and cooling season, the
following service checks should be performed by a
qualified service technician. First, turn off electrical power
to the unit prior to performing unit maintenance.

WARNING

Electric shock hazard.

Can cause injury or death.

Before attempting to perform any
service or maintenance, turn the
electrical power to unit OFF at
disconnect switch(es). Unit may have
multiple power supplies.

S

Inspect and clean the outdoor and indoor coils. The
outdoor coil may be flushed with a water hose.

NOTE − It may be necessary to flush the outdoor coil
more frequently if it is exposed to substances which
are corrosive or which block airflow across the coil
(e.g., pet urine, cottonwood seeds, etc.)

S

Visually inspect the refrigerant lines and coils for leaks.

S

Check wiring for loose connections.

S

Check voltage at the indoor and outdoor units (with
units operating).

S

Check the amperage draw at the outdoor fan motor,
compressor, and indoor blower motor. Values should
be compared with those given on unit nameplate.

S

Check, clean (or replace) indoor unit filters.

S

Check the refrigerant charge and gauge the system
pressures.

S

Check the condensate drain line for free and
unobstructed flow; clean, if necessary.

S

Outdoor unit fan motor is prelubricated and sealed. No
further lubrication is needed.

NOTE − If owner reports insufficient cooling, the unit
should be gauged and refrigerant charge checked.
Refer to section on refrigerant charging in this
instruction.

Homeowner Information

In order to ensure peak performance, your system must be
properly maintained. Clogged filters and blocked airflow
prevent your unit from operating at its most efficient level.

1.

Air Filter

Ask your Lennox dealer to show you where

your indoor unit’s filter is located. It will be either at the
indoor unit (installed internal or external to the cabinet)
or behind a return air grille in the wall or ceiling. Check
the filter monthly and clean or replace it as needed.

2.

Disposable Filter

Disposable filters should be

replaced with a filter of the same type and size.

NOTE − If you are unsure about the filter required for
your system, call your Lennox dealer for assistance.

IMPORTANT

Turn off electrical power to the unit at the
disconnect switch before performing any
maintenance. The unit may have multiple power
supplies.

3.

Reusable Filter

Many indoor units are equipped

with reusable foam filters. Clean foam filters with a

Содержание Signature XP15-024

Страница 1: ...ping and Packing List 1 Unit Dimensions 2 General Information 2 Recovering Refrigerant from Existing System 4 Positioning New Outdoor Unit 5 Removing Panel 6 Electrical Connections 7 New or Replacemen...

Страница 2: ...will expose you to fiberglass wool dust Breathing this may cause lung cancer Fiberglass wool is known to the State of California to cause cancer Fiberglass wool may also cause respiratory skin and eye...

Страница 3: ...rvice Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap using an appropriately sized wrench 2 Connect gauge to the...

Страница 4: ...e 90 To close rotate Stem clockwise 90 Service Port Service Port Cap STEM CAP Valve Stem Open to line set when valve is closed to both line set and unit when valve is open Figure 3 Ball Type Service V...

Страница 5: ...r as possible from the property line When possible do not install the unit directly outside a window Glass has a very high level of sound transmission For proper placement of unit in relation to a win...

Страница 6: ...side louvered panels to expose the unit base pan Install the brackets as illustrated in figure 10 using conventional practices replace the panels after installation is complete IMPORTANT Using field p...

Страница 7: ...panel firmly throughout this procedure Rotate bottom corner of panel away from hinged corner post until lower three tabs clear the slots as illustrated in figure 12 detail B 3 Move panel down until li...

Страница 8: ...pply to unit from a properly sized disconnect switch as illustrated in figure 15 4 Ground unit from ground lug as illustrated in figure 15 to unit disconnect switch or to an earth ground Figure 14 Typ...

Страница 9: ...te the following points S Model XP15 and size e g 060 of unit S Line set diameters for the unit being installed from table 3 S Number of elbows and if there is a rise or drop of the piping Line sets f...

Страница 10: ...ruction Shown STRAP LIQUID LINE TO VAPOR LINE METAL SLEEVE AUTOMOTIVE MUFFLER TYPE HANGER WALL STUD VAPOR LINE WRAPPED IN ARMAFLEX LIQUID LINE ANCHORED HEAVY NYLON WIRE TIE STRAP LIQUID LINE TO VAPOR...

Страница 11: ...o protect the base paint Also shield the light maroon R 410A sticker 5 Flow regulated nitrogen at 1 to 2 psig through the refrigeration gauge set into the valve stem port connection on the liquid line...

Страница 12: ...gerant added to the system earlier is measurable with a leak detector 11 After leak testing disconnect gauges from service ports Removing Service Valve Port Core Remove both of the outdoor unit s serv...

Страница 13: ...system NOTE A single system flush should remove all of the mineral oil from the existing refrigerant lines and indoor unit coil A second flushing may be done using clean refrigerant if insufficient am...

Страница 14: ...nit s service port cores liquid and vapor as illustrated in figure 24 DO NOT INSTALL CAPS AT THIS TIME INSTALL SERVICE PORT CORES OUTDOOR UNIT LIQUID AND VAPOR SERVICE VALVES Figure 24 Typical Service...

Страница 15: ...er evacuation is complete open the liquid line and vapor line service valves to release the refrigerant charge contained in outdoor unit into the system 4 Replace the stem caps and tighten as specifie...

Страница 16: ...4 Adjust the fan speed See indoor unit instructions to in crease decrease fan speed Changing air flow affects all temperatures recheck tempera tures to confirm that the temperature drop and DT are wit...

Страница 17: ...record it in the SAT space 8 Subtract LIQ temp from SAT temp to determine subcooling record it in SC space 9 Compare SC results with table below being sure to note any additional charge for line set...

Страница 18: ...48C 7 5 0 7 CH33 49C 5 5 0 12 CH33 62D 5 7 0 14 CR33 48C 37 4 0 5 CR33 50 60 32 5 0 10 CX34 31 15 4 0 0 CX34 38 SN 6007 and after 4 4 0 3 CX34 38 before SN 6007 13 4 0 3 CX34 43 7 5 0 7 CX34 44 48 13...

Страница 19: ...GHT An emergency heat function is designed into some room thermostats This feature is applicable when isolation of the outdoor unit is required or when auxiliary electric heat is staged by outdoor the...

Страница 20: ...running only briefly 1 Thermostat demand signal is intermittent 2 Time delay relay or DCB is defective 3 If high pressure switch is present see Flash Code 2 information 4 If low pressure switch is pre...

Страница 21: ...Check or Service LED or it may come on solid Confirm fault by observing and interpreting the code from the LSOM yellow alert LED at the unit Defrost System DEFROST CONTROL BOARD DCB FUNCTION The DCB...

Страница 22: ...nal sounds that may occur while the unit is cycling in and out of the defrost mode When a jumper is installed on the DELAY pins the compressor will be cycled off for 30 seconds going in and out of the...

Страница 23: ...istance values can be checked by ohming across pins shown in table 15 NOTE When checking the ohms across a sensor be aware that a sensor showing a resistance value that is not within the range shown i...

Страница 24: ...e installed or incorrect operation of metering de vice 4 Incorrect or improper sensor location or connection to system 1 Remove any blockages or restrictions from coils and or fans Check indoor and ou...

Страница 25: ...the Demand Defrost Control Y1 Active Place a jumper on TEST pins for longer than one second but less than two seconds Clears any short cycle lockout and five strike fault lockout function if applicabl...

Страница 26: ...the start of each heating and cooling season the following service checks should be performed by a qualified service technician First turn off electrical power to the unit prior to performing unit mai...

Страница 27: ...ing cycle when temperatures are below 45 F 7 C An electronic control activates a defrost cycle lasting 5 to 15 minutes at preset intervals to clear the outdoor coil of the frost S During the defrost c...

Страница 28: ...5 include the following also see Engineering Handbook for more details S Compressor starter kit S Low ambient kit S Vapor line drier S Wire tie kit S Snow Guard X8782 S Snow Shield Kit 44W14 Start Up...

Отзывы: