background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

14

Step 3. Center outer-locking section over outer
chimney pipe. Push down until locking joint
has firmly engaged.

Step 4. Pull up slightly on return elbow to
ensure locking joint has firmly engaged.

Step 5. Secure support straps to framing
members by nailing under tension in sheer
(

Figure 40 ).

Return

Elbow

AIR INLET
EYEBROW
ASSEMBLY

FOAK

Figure 41

Figure 42

Figure 40

Step 3. The air inlet for the outside air kit is
located on the right hand side of the fireplace
(

Figure 42 ).  Refer to the installation instruc-

tions packed with each FOAK-4 air kit for
specific installation information. The outside
air kit, if used, must be installed before the
fireplace is totally framed and enclosed within
the finished walls.

Note: The return elbow assembly performs
the same function as a stabilizer. Consider this
when determining the need for a stabilizer.

Note: Do not apply excessive pressure to any
subsequent chimney section following return
elbow assembly when installing. Ensure that
each subsequent chimney section is securely
attached by testing as noted above.

Combustion Air Kits

The installation of an outside combustion air
kit is highly recommended.  It is very impor-
tant to ensure good fireplace operation in
homes which are tightly weather sealed or
have ventilating appliances installed.

Step 1. Determine the source for outside air,
which can be installed through an outside wall
or into a ventilated crawl space.  In either case,
a 4 1/2" diameter hole will be required for
installation of the air inlet assembly.

CAUTION: AVOID INSTALLING THE AIR IN-
LET WHERE THE OPENING COULD BE
BLOCKED BY SNOW, BUSHES OR OTHER
OBSTACLES.  THE MAXIMUM HEIGHT FOR
THE OUTSIDE AIR IS 50 FEET ABOVE THE
HEARTH, PROVING THE AIR INLET IS TERMI-
NATED A MINIMUM OF THREE (3) FEET BE-
LOW THE CHIMNEY CAP LEVEL.

Note: Combustion air inlet ducts must not
terminate in attic space.

Step 2. Install the air inlet eyebrow (FOAK-4 or
FOAK-4LD) through the wall opening (

Figure 41).

Push a 4 inch diameter NON-COMBUSTIBLE
Class 0 or Class I flexible duct onto the eyebrow.

Figure 38

Figure 39

Underside Of Chimney

Note: See Framing and Dimension Chart for
the sizes of the ceiling and roof openings. The
size of the roof opening varies with the degree
of pitch of the roof.

Offset Elbow Assembly

Offset elbows install the same as chimney
sections. First, snap the inner section INTO the
preceding inner section of flue. Check connec-
tion by pulling up slightly to ensure a tight fit.
Next, the outer sections snap lock OVER the
preceding outer section of chimney. Again,
check outer section by pulling up slightly to
ensure proper connection is made.

Return Elbow Assembly

Return elbows install the same way as round
terminations and stabilizers:

Step 1. Hold return elbow over top of last
chimney section.

Step 2. Center inner slip section into inner flue
pipe-slip down.

Chimney Section (S)

FTF13-E30 Return Elbow*

FTF13-30 Offset Elbow*

B

A

*Part of Offset/Return Package Model FTF13-ES30

After completing the installation of the optional
combustion air vent system, the actuator arm
must be put in service and tested to ensure
proper operation before completing any enclo-
sure around the firebox.  Failure to do so may
result in extensive and costly rework.

To operate, locate the hand operated shut-off
lever at the lower right side of the fireplace
opening behind the screen.  To open the air
damper, turn upwards.  To close, turn down.

Operate the actuator through several cycles.
Ensuring proper operation and freedom of
movement.  Return the actuator arm to the
closed position.

OPEN

CLOSED

Содержание Signature CollectionEST-48-H ESTATE SERIES

Страница 1: ...its components under any circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney components and accessories may void the warranty listi...

Страница 2: ...damage as a result of handling or transporta tion These items should be inspected by your distributor or qualified factory representative to ensure safe condition When in doubt con sult your distribu...

Страница 3: ...obile homes These fireplace systems are designed for in stallation in accordance with the National Fire Protection Standard for chimneys fireplaces and solid fuel burning appliances NFPA 211 and in ac...

Страница 4: ...amper is controlled through the use of a control lever located within the firebox opening at the top center just behind the firebox lintel Figure 3 The control lever snaps into place at the ex treme r...

Страница 5: ...e Zone 45 12 Door Opening 1 12 The safety strips should extend from front of the fireplace at least 2 and should extend to be at least flush with the sides In the event a wooden support is used to ele...

Страница 6: ...to be attached to the rear wall then the framed depth must be measured from the drywall surface It is important that this dimension be exact If the appliance is to be elevated above floor level a sol...

Страница 7: ...igure 14 A B Ceiling Framing C D Roof Framing Corner Installation K D A E F Back Wall of Chase Enclosure Including Finising Materials if any Rough Framing Face Unfinished Shown FOAK Combustion Air Kit...

Страница 8: ...chimney use 30 firestop spacer Model F10FS30 2 Use one nail on opposite sides to hold firestop spacer in position Nail permanently using at least two 2 more 8d nails after chimney sections have been a...

Страница 9: ...ding flue pipe and locking outer stabi lizer section into place over the outer chimney pipe Position for proper clearance through framedopeningandnailstrapssecurely under tension in shear into place o...

Страница 10: ...ng tabs are firmly engaged 4 PullupslightlyonCTDtoensurelockingjoint has firmly engaged Using a FTF13 CT1 Chase Termination Refer to specific installation instructions in cluded with FTF13 CT1 chase t...

Страница 11: ...is 15 6 higher with offsets The maximum height for the system is 80 To determine the number of chimney sections andchimneycomponentsrequired followthese steps 1 Determine the total vertical height of...

Страница 12: ...hes Feet Inches 12 18 36 MM M 461 38 5 0 1 13 11722 11 72 465 38 9 2 0 13 11824 11 82 471 39 3 1 1 13 11976 11 98 479 39 11 0 0 14 12179 12 18 489 40 9 1 0 14 12433 12 43 495 41 3 0 1 14 12586 12 59 4...

Страница 13: ...2178 45 87 1 0 0 3 1 1149 2223 46 89 1 0 0 1 2 1175 2261 48 91 1 0 2 0 2 1226 2324 49 94 1 0 1 5 0 1257 2400 51 97 1 0 1 1 2 1302 2483 54 103 1 0 0 2 2 1378 2616 55 104 1 0 0 0 3 1403 2654 56 106 1 0...

Страница 14: ...E OUTSIDE AIR IS 50 FEET ABOVE THE HEARTH PROVING THE AIR INLET IS TERMI NATED A MINIMUM OF THREE 3 FEET BE LOW THE CHIMNEY CAP LEVEL Note Combustion air inlet ducts must not terminate in attic space...

Страница 15: ...surface of the indentation The refrac torymaterialisverythininthisareaandiseasily removed Once a small hole has been made continue tapping until you have reached suffi cientdiameterforthegaslinetofit...

Страница 16: ...ick must this material be Using the k formula Desired k value of desired Min Thickness Required material per inch x of listed Thickness k value of listed material material per inch TM inches kM x T1 8...

Страница 17: ...0 2 Offset Return Package 30 63L24 FTF13 ES30 INSTALLATION COMPONENTS The following items are available for use in the installation of this appliance The sum of all R values is 70 10 068 5825 1 4505 T...

Страница 18: ...9 FTF13 12 63L20 FTF13 18 Chimney Section 63L21 FTF13 36 63L40 F10F6 Flashing 63L41 F10F12 Round Termination 63L44 FTF13 CTD Firestop Spacer Flat 63L36 F10FS 2 INSTALLATION COMPONENTS Storm Collar 63L...

Страница 19: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 19...

Страница 20: ...ges at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information Printed in U S...

Отзывы: