NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

3

Figure 1

TYPICAL INSTALLATION

*Construction Materials:

• framing materials

• paneling

• particle board

• flooring

• millboard

• dry wall

• plywood

• etc.

PRECAUTIONS

Note: These fireplace systems are not difficult
to install. However, in the interest of safety, it
is recommended that the installer be a quali-
fied or certified “tradesman” familiar with com-
monly accepted fireplace installation and safety
techniques as well as prevailing local codes.

The most important areas of concern dealing
with the installation of factory-built fireplaces
are clearances to combustible materials, proper
assembly of component parts, height of the
chimney system, the proper use of accesso-
ries supplied by the manufacturer and the
techniques employed in using finishing mate-
rials applied to the wall surrounding the fire-
place, hearth extensions and wall shields. Each
of these topics will be covered in thorough
detail throughout this manual. Please give
each your special attention as you progress
with your installation.

INTRODUCTION
General Information

These fireplaces are conventional radiant heat
fireplaces with standard bar grates, optional
outside combustion air kits and optional deco-
rative glass doors.

Note: Illustrations shown reflect “typical” instal-
lations with nominal dimensions and are for
design and framing reference only. Actual instal-
lations may vary due to individual design prefer-
ences. However, always maintain minimum clear-
ances to combustible materials and do not vio-
late any specific installation requirements.

These fireplaces have been tested and listed by
Warnock Hersey (Report No. 629-915173) to
U.L. standard 127. These units are intended
for installation in residential homes and other
buildings of conventional construction includ-
ing commercial, not in mobile homes.

These fireplace systems are designed for in-
stallation in accordance with the National Fire
Protection Standard for chimneys, fireplaces
and solid fuel burning appliances; NFPA 211
and in accordance with codes such as the
BOCA Basic/National Codes, the Standard Me-
chanical Code and the Uniform Building Codes.

WARNING: FAILURE TO USE MANUFAC-
TURE PROVIDED PARTS, VARIATIONS IN
TECHNIQUES AND CONSTRUCTION MA-
TERIALS OR PRACTICES OTHER THAN
THOSE DESCRIBED IN THIS MANUAL
MAY CREATE A FIRE HAZARD AND VOID
THE LIMITED WARRANTY.

When complete these fireplace systems con-
sists of four basic “sub-systems”:

1. The Fireplace
2. The Chimney and Termination
3. The Optional Glass Doors
4. The Optional Combustion Air Kits

CLEARANCES AND HEIGHT
REQUIREMENTS

The fireplace may be placed on or near normal
construction materials*. The combustion air
kit, firestop spacer and roof flashing (not chase
flashings) may be placed directly on or against
normal construction materials.* The chimney
and fireplace outer wrapper require a mini-
mum 2" air space to combustibles. A combus-
tible mantle may be installed 12" above the
opening of the fireplace as per NFPA 211,
Section 7-2.3.3.

The minimum installed height of the completed
fireplace system is 15' 6".  The maximum height
is 80' 0".

The fireplace and chimney system must be
enclosed when installed in or passing through
a living area where combustibles or people may
come in contact with it. This is important to
prevent possible personal injury or fire hazard.

For questions, please call your distributor or
the manufacturer. Special restrictions apply to
the front and facing of the fireplace and nearby
walls (See pages 16 and 17 ).

CHIMNEY SYSTEM

These fireplaces are designed and code listed
for use with Security Chimneys FTF13 chimney
System only.  Always use Security Chimneys
FTF13 chimney components with these fire-
places.  Do not modify or alter these compo-
nents as this may cause a potential serious
hazard and void the Warranty.

Chimney and
Termination

Содержание Signature CollectionEST-48-H ESTATE SERIES

Страница 1: ...its components under any circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney components and accessories may void the warranty listi...

Страница 2: ...damage as a result of handling or transporta tion These items should be inspected by your distributor or qualified factory representative to ensure safe condition When in doubt con sult your distribu...

Страница 3: ...obile homes These fireplace systems are designed for in stallation in accordance with the National Fire Protection Standard for chimneys fireplaces and solid fuel burning appliances NFPA 211 and in ac...

Страница 4: ...amper is controlled through the use of a control lever located within the firebox opening at the top center just behind the firebox lintel Figure 3 The control lever snaps into place at the ex treme r...

Страница 5: ...e Zone 45 12 Door Opening 1 12 The safety strips should extend from front of the fireplace at least 2 and should extend to be at least flush with the sides In the event a wooden support is used to ele...

Страница 6: ...to be attached to the rear wall then the framed depth must be measured from the drywall surface It is important that this dimension be exact If the appliance is to be elevated above floor level a sol...

Страница 7: ...igure 14 A B Ceiling Framing C D Roof Framing Corner Installation K D A E F Back Wall of Chase Enclosure Including Finising Materials if any Rough Framing Face Unfinished Shown FOAK Combustion Air Kit...

Страница 8: ...chimney use 30 firestop spacer Model F10FS30 2 Use one nail on opposite sides to hold firestop spacer in position Nail permanently using at least two 2 more 8d nails after chimney sections have been a...

Страница 9: ...ding flue pipe and locking outer stabi lizer section into place over the outer chimney pipe Position for proper clearance through framedopeningandnailstrapssecurely under tension in shear into place o...

Страница 10: ...ng tabs are firmly engaged 4 PullupslightlyonCTDtoensurelockingjoint has firmly engaged Using a FTF13 CT1 Chase Termination Refer to specific installation instructions in cluded with FTF13 CT1 chase t...

Страница 11: ...is 15 6 higher with offsets The maximum height for the system is 80 To determine the number of chimney sections andchimneycomponentsrequired followthese steps 1 Determine the total vertical height of...

Страница 12: ...hes Feet Inches 12 18 36 MM M 461 38 5 0 1 13 11722 11 72 465 38 9 2 0 13 11824 11 82 471 39 3 1 1 13 11976 11 98 479 39 11 0 0 14 12179 12 18 489 40 9 1 0 14 12433 12 43 495 41 3 0 1 14 12586 12 59 4...

Страница 13: ...2178 45 87 1 0 0 3 1 1149 2223 46 89 1 0 0 1 2 1175 2261 48 91 1 0 2 0 2 1226 2324 49 94 1 0 1 5 0 1257 2400 51 97 1 0 1 1 2 1302 2483 54 103 1 0 0 2 2 1378 2616 55 104 1 0 0 0 3 1403 2654 56 106 1 0...

Страница 14: ...E OUTSIDE AIR IS 50 FEET ABOVE THE HEARTH PROVING THE AIR INLET IS TERMI NATED A MINIMUM OF THREE 3 FEET BE LOW THE CHIMNEY CAP LEVEL Note Combustion air inlet ducts must not terminate in attic space...

Страница 15: ...surface of the indentation The refrac torymaterialisverythininthisareaandiseasily removed Once a small hole has been made continue tapping until you have reached suffi cientdiameterforthegaslinetofit...

Страница 16: ...ick must this material be Using the k formula Desired k value of desired Min Thickness Required material per inch x of listed Thickness k value of listed material material per inch TM inches kM x T1 8...

Страница 17: ...0 2 Offset Return Package 30 63L24 FTF13 ES30 INSTALLATION COMPONENTS The following items are available for use in the installation of this appliance The sum of all R values is 70 10 068 5825 1 4505 T...

Страница 18: ...9 FTF13 12 63L20 FTF13 18 Chimney Section 63L21 FTF13 36 63L40 F10F6 Flashing 63L41 F10F12 Round Termination 63L44 FTF13 CTD Firestop Spacer Flat 63L36 F10FS 2 INSTALLATION COMPONENTS Storm Collar 63L...

Страница 19: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 19...

Страница 20: ...ges at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information Printed in U S...

Отзывы: